HomeMy WebLinkAbout_SOLR23-0506_Mickell Permit PackageSignature of Licensed Preparer Mickell Residence 318 Appaloosa Way Palm Desert, CA 92211 14.0 kw DC, 12.612 kw AC 35 Q.PEAK DUO BLK ML-G10+ 400 35 IQ8A-72-2-US Square D Shingle IronRidge 3/25/23 Size: Modules: Inverter: AC Dis.: Roof: Racking: Date: RD Winkle Co PO Box 470 Thousand Palms, CA 92276 760-272-0003 CA License #688062 C46, C39 DWG# 1 Cover Sheet DWG# 2 Site Plan DWG# 3 Layout DWG# 4 Electrical Diagram DWG# 5 CEC Calculations DWG# 6 General Notes DWG# 7 System Labels Product Spec Sheets 14.0 kw Roof Mounted Photovoltaic Mickell Residence 318 Appaloosa Way Palm Desert, CA 92211 35 QCell 400 Watt Panels Drawing Number: 1 Signature of Licensed Preparer Mickell Residence 318 Appaloosa Way Palm Desert, CA 92211 14.0 kw DC, 12.612 kw AC 35 Q.PEAK DUO BLK ML-G10+ 400 35 IQ8A-72-2-US Square D Shingle IronRidge 3/25/23 Size: Modules: Inverter: AC Dis.: Roof: Racking: Date: RD Winkle Co PO Box 470 Thousand Palms, CA 92276 760-272-0003 CA License #688062 C46, C39 3' 3' 18" 18" Drawing Number: 2 Site Plan Main Service Panel AC Disconnect AC Combiner Solar Modules Pr o p e r t y L i n e Pr o p e r t y L i n e Property Line Property Line Signature of Licensed Preparer Mickell Residence 318 Appaloosa Way Palm Desert, CA 92211 14.0 kw DC, 12.612 kw AC 35 Q.PEAK DUO BLK ML-G10+ 400 35 IQ8A-72-2-US Square D Shingle IronRidge 3/25/23 Size: Modules: Inverter: AC Dis.: Roof: Racking: Date: RD Winkle Co PO Box 470 Thousand Palms, CA 92276 760-272-0003 CA License #688062 C46, C39 2'-0" Drawing Number: 3 Layout IronRidge FlashvueRafterSupport Rail Solar Module Basic Wind Speed: Risk Category IV - 108 mph IronRidge RailShingle Under layment 5 16" X 31 2" Lag Screw with 21 2" minimum embedment Weather sealant in pilot hole 2" X 4" Rafter 24" O.C. Solar Module IronRidge Flashvue Max spacing on solar roof attachments = 72" Signature of Licensed Preparer Mickell Residence 318 Appaloosa Way Palm Desert, CA 92211 14.0 kw DC, 12.612 kw AC 35 Q.PEAK DUO BLK ML-G10+ 400 35 IQ8A-72-2-US Square D Shingle IronRidge 3/25/23 Size: Modules: Inverter: AC Dis.: Roof: Racking: Date: RD Winkle Co PO Box 470 Thousand Palms, CA 92276 760-272-0003 CA License #688062 C46, C39 Permanent placard shall be placed at main service breaker stating "MAIN SERVICE BREAKER HAS BEEN DOWNSIZED TO 175 AMPS. NO UPSIZING IS PERMITTED." Main Service Panel is fed from top of the busbar. Solar Inverter breaker will be located at the opposite end of the busbar per NEC 705.12(B)(3)(2) PV MODULE RATINGS @ STC 1 System Summary Service Main: 200 Amps Main OCPD Rating: 175 Amps Service Voltage: 240 Volts PV System Size: 14.0 kW # of Branch Circuits: 4 Branch Circuits Inverter BackFeed Breaker: 70 Amps PV System Azimuth: 180°, 270° PV System Tilt: 18° L2 L1 G L2 L1 AC Disconnect 3 70 AMP 2 pole breaker Typical Neutral-to-ground Connection point If Existing Earth Ground is not accessible, an irreversible splice will be made to the Grounding Electrode Conductor 175 AMP 2 pole breaker Existing Earth Ground To Utility L1 L2 G N L2L1 G N Utility-Supplied 240 VAC KWH Meter +-+- +-+-+-+-+-+-+- +-+-+-+-+- 100 Amp AC Combiner THWN-2 8 - #10 AWG 1 - #8 AWG EGC 3/4" EMT 20 AMP 2 pole breaker Junction Box 1 L2L1 G N 20 AMP 2 pole breaker +-+-+- +- +-+-+- 20 AMP 2 pole breaker +-+-+-+-+- +-+-+- Racking Integrated Grounding System Bonds Solar Panel Frames to Support Rail +-+-+-+- +- +- 20 AMP 2 pole breaker Note: Enphase MicroInverters meet CEC 690.12 Rapid Shutdown Requirements #6 Bare Copper Ground under array where exposed. Inside junction box it will be permanently bonded to #8 AWG Stranded Ground which will run through EMT conduit with conductors. AC DISCONNECT RATINGS MANUFACTURER= SQUARE D MODEL= DU323RB DISCONNECT AMP RATING= 100 A DISCONNECT VOLT RATING= 240 V 3 THWN-2 3 - #6 AWG 1 - #4 AWG EGC 1" EMT Enphase IQ8A MicroInverters 2 Support Rail AC Line 2 AC Line 1 Bare CopperDC Negative DC Positive Legend AC NeutralEquip. Ground INVERTER RATINGS 2 ENPHASE IQ8A-72-2-US MAX DC VOLT RATING= 60 V MAX POWER= 366 W NOMINAL AC VOLTAGE= 240 V MAX AC CURRENT= 1.45 A MAX OCPD RATING= 20 A FREQUENCY = 60 HZ MODULE MANUFACTURER= QCell MODULE MODEL= Q.PEAK DUO BLK ML-G10+ 400 OPEN-CIRCUIT VOLTAGE= 45.30 V OPERATING VOLTAGE= 37.13 V MAX SYSTEM VOLTAGE= 1000 V OPERATING CURRENT= 10.77 A SHORT-CIRCUIT CURRENT= 11.14 A MAX SERIES FUSE(OCPD)=20 A MAXIMUM POWER (@25°C)= 400 W Existing Main Service Panel 200 amp busbar 175 amp main breaker Inverter output x 1.25 = 63.44 amps 200 x 120% = 240 amps 175 + 63.44 = 238.44 amps Drawing Number: 4 Electrical Diagram Signature of Licensed Preparer Mickell Residence 318 Appaloosa Way Palm Desert, CA 92211 14.0 kw DC, 12.612 kw AC 35 Q.PEAK DUO BLK ML-G10+ 400 35 IQ8A-72-2-US Square D Shingle IronRidge 3/25/23 Size: Modules: Inverter: AC Dis.: Roof: Racking: Date: RD Winkle Co PO Box 470 Thousand Palms, CA 92276 760-272-0003 CA License #688062 C46, C39 Inverter Output Circuit: Enphase IQ8A-72-2-US Inverter Max Continuous Current = 1.45 A Inverter output circuit over current protection = 20 A breaker 125% of inverter max continuous output circuit = 125% x 1.45 x 10 = 18.13 A Output circuit continuous current = 18.13 A < 20 A Inverter output circuit over current protection = 20 A breaker 125% of inverter max continuous output circuit = 125% x 1.45 x 9 = 16.31 A Output circuit continuous current = 16.31 A < 20 A Inverter output circuit over current protection = 20 A breaker 125% of inverter max continuous output circuit = 125% x 1.45 x 7 = 12.69 A Output circuit continuous current = 12.69 A < 20 A Inverter output wiring to dedicated inverter circuit breaker = (1 sets) #10 THWN-2, 90 degrees C rated Conductors will be more than 7/8" above the roof surface. Temperature correction factor for 40 degree C = 0.91 Correction factor for 8 current-carrying conductors = 0.7 Corrected ampacity = 40 A x 0.91 x 0.7 = 25.48 A > 20 A Voltage Drop for branch circuit of 10 microinverters: One way distance from array to AC combiner is 100 feet. Conductor length = 100 x 2 = 200 feet Resistance on conductors = (1.29/1000) x 200 = .258 Ohms Voltage drop = (10 x 1.45) x .258 = 3.74 volts Voltage drop % = (3.74/240) x 100 = 1.56% Combined Inverter Output Circuits Interconnection circuit breaker for AC Combiner output = 70 A 125% of inverter max continuous output circuit = 125% x 1.45 x 35 = 63.44 A Output circuit continuous current = 63.44 A < 70 A AC Combiner output wiring to point of interconnection at Main Service Panel = (1 sets) #4 THWN-2, 90 degrees C rated Temperature correction factor for 40 degrees C ambient = 0.91 Corrected ampacity = 95 A x 0.91 = 86.45 A > 70 A 6\VWHP'HVFULSWLRQ Enclosed documents describe requirements for a new Photovoltaic (PV) system. PV equipment location shall be coordinated with owner's representative. All wires to transition boxes shall be routed within metallic cable tray system. Length, gauge and type of wire is indicated on "Electrical Diagram" drawing. Output from grid-tied inverters may be combined in an AC combiner panel then interconnected with the grid power (in concordance with CEC 690.59). If used, the AC combiner will be shown on the "Electrical Diagram" drawing. The complete PV system described here shall be installed and commissioned such that it operates automatically as follows: 1.When grid power is present, solar power runs loads onsite during the day. 2.When grid power fails, the PV system shall automatically disconnect from the grid. 3.The PV system shall automatically resume supplying power to the grid when the proper voltage and frequency (As mandated by the IEEE standards) is restored and there is sufficient sunlight. DC Voltage QCell Q.PEAK DUO BLK ML-G10+ 400 PV Module Voc = 45.30 VDC STC PV Module Vpm = 37.13 VDC STC Maximum number of PV Modules per string = 1 Nominal Maximum Power Voltage = 37.13 x 1 = 37.13 V Correction factor per CEC 690.7 (A) for -5 degree C = 1.12 x (PV module Voc AT 25 degree C) = 50.74 V Maximum Open Circuit Voltage = 1 x 50.74 = 50.74 V PV Source Circuit PV module Isc = 11.14 A PV module Imp = 10.77 A # of modules in parallel per source circuit = 1 Max Isc = 1 x 11.14 A x 1.25 = 13.93 A Drawing Number: 5 Electrical Calculations Signature of Licensed Preparer Mickell Residence 318 Appaloosa Way Palm Desert, CA 92211 14.0 kw DC, 12.612 kw AC 35 Q.PEAK DUO BLK ML-G10+ 400 35 IQ8A-72-2-US Square D Shingle IronRidge 3/25/23 Size: Modules: Inverter: AC Dis.: Roof: Racking: Date: RD Winkle Co PO Box 470 Thousand Palms, CA 92276 760-272-0003 CA License #688062 C46, C39 1.All Electrical work shall be in accordance with the 2022 Editions of the California Building Code, California Electrical Code (CEC) , California Plumbing Code, California Mechanical Code, California Fire Code and the California Energy Code, local municipal code, and local fire district regulations. 2.Applications for which no permit is issued within 180 days following the date of application shall automatically expire. 3.Every permit issued shall become invalid unless work authorized is commenced within 180 days, a successful inspection is not obtained within 180 days, or if work is suspended or abandon for a period of 180 days. 4.All equipment shall be listed and labeled per recognized electrical testing laboratory and installed per the listing requirements and the manufacturer's instructions. 5.All inverters shall be UL 1741 compliant and shall be inspected by local utility before commissioning, testing, and operation of the system. 6.All outdoor equipment shall be minimum NEMA 3R, including outdoor transition boxes, combiner boxes, and switches. 7.All equipment shall be properly grounded per the requirements of CEC ART. 250, 690. 8.All circuits shall have overcurrent protection as required by CEC ART.690.9 (A). 9.Due to the fact that PV modules are energized whenever they are exposed to light, PV contractors shall enable the array during installation and service by short circuiting, opening circuiting, or covering the array with an opaque covering. 10.Photovoltaic system shall back feed the distribution system on site per the requirements of CEC ART. 705. All back feed breakers shall be identified as such. 11.Fall arrest protection per OSHA requirements shall be provided for all roof work. 12.All conductors and termination shall be rated for 75 degree C minimum. 13.CEC ART. 705.10 A permanent plaque or directory denoting the location of all electric power source disconnecting means on or in the premises shall be provided at each service equipment location and at the location(s) of the system disconnect(s) for all electric power production sources capable of being interconnected. The marking shall comply with CEC ART. 110.21 (B). 14.CEC ART. 690.13 (B) each DC disconnect shall be labeled with: "PV System Disconnect." Label shall be 1" x 4" minimum with UV resistant lettering per local municipal code. 15.CEC ART. 690.53 A placard, UV resistant, and lettering per local municipal code, shall be provided beside the dc disconnect location with the following text: Maximum voltage = XXX VOLTS, Maximum Short circuit current = XXX AMPS 16.CEC ART. 690.13 (B) Each AC disconnect shall be labeled with: "PV System Disconnect." Label shall be 1" x 4" minimum with UV resistant lettering per local municipal code. 17.CEC ART. 690.13 (B) Each disconnect where both line and load sides may be energized in the open positions shall also be labeled with: "Warning! - Electrical shock hazard - Do not touch terminals on both line and load side may be energized in the open position". Label shall be 1" x 4" minimum with UV resistant lettering per local municipal code. 18.DC disconnect at the inverter shall be readily accessible after the installation is complete per CEC ART.690.13 (A). 19.Contractor to provide ground fault protection for photovoltaic arrays per CEC ART. 690.41 (B) 20. Contractor to provide Arc fault protection for all photovoltaic systems operating at 80 volts DC or greater per CEC ART. 690.11. 21.Where more than one nominal voltage system exists, the different Systems shall be identified by phase and system per CEC ART. 215.12 (C). 22.Provide an accessible disconnect device that is lockable in open position and is located within 10' - 0" of the meter per local electrical utility regulations. 23.Photovoltaic source currents must be rated at both 125% of the parallel module and at a continuous load of another 125% for a total of 156% of the load. 24.Installation of PV panel arrays should resist sliding and pop-up resulting from seismic events and should comply with CBC section 1613A and ASCE standard 7-16, Chapter 13. 25.Design indicates use of copper wire for DC circuits, use of aluminum wires is not allowed. 26.It is recommend to install the PV array such that general shading of the PV modules between 9:00 am - 3:00 pm solar is minimized and localized shading due to plumbing or air vents is minimized. 27.PV system installer will be responsible for furnishing and installation of all related equipment, cables, additional conduits, boxes wireways and other accessories necessary for complete and operational photovoltaic system. 28.PV system contractor shall coordinate all the work with the engineer, the construction manager and all other contractors to insure that PV system is installed as specified in these drawings. 29.Drawings in general are diagrammatic and indicate general arrangement of the equipment and work included. The intention of the drawings is to indicate size, capacity, approximate location and general relationship, but not exact detail or physical placement. 30.Field verify exact AC rating required of the main switchboard from local utility company. 31.Notify serving utility before activation of pv system. 32.Working clearances around existing electrical equipment as well as the new electrical equipment will be maintained in accordance with CEC 110.26. 33.Per section R314 and R315 of CRC 2019, it is required that Smoke alarm and Carbon Monoxide Detectors are retrofitted into existing dwelling for a permit with repairs or additions exceeding $1000. 34.Wiring methods will be according to CEC ART. 690.31. All raceways and cables, fittings specifically intended and identified for use on photovoltaic systems. Direct current and alternating currents shall be separated by barriers to meet code requirements. 35.Circuits over 150 volts to ground in one and two family dwellings, live parts in photovoltaic source circuits and photovoltaic output circuits over 150 volts to ground shall not be accessible to other than qualified persons while energized. 36.Point of connection CEC ART. 705.12 (B) Inverter Output Connection in a panelboard shall be positioned at the opposite (load) end from the input feeder location or main circuit location. A permanent label shall be applied to the distribution equipment with the following or equivalent markings. "WARNING INVERTER OUTPUT CONNECTION DO NOT RELOCATE THIS OVERCURRENT DEVICE" 37.Conduit wiring systems, and raceways for photovoltaic circuits shall be located as close as possible to the ridge or hip or valley and from the hip or valley as directly as possible to an outside wall to reduce trip hazards and maximize ventilation opportunities. Conduit runs between sub arrays and to DC combiner boxes shall be installed in a manner that minimizes the total amount of conduit on the roof by taking the shortest path from the array to the DC combiner box. The DC combiner boxes shall be located such that conduit runs are minimized in the pathways between arrays. DC wiring shall be installed in metallic conduit or raceways when located within enclosed spaces in a building. Conduit shall run along the bottom of load bearing members. 38.Electric utility company servicing building shall be notified prior to operation of the PV system. Drawing Number: 6 General Notes Signature of Licensed Preparer Mickell Residence 318 Appaloosa Way Palm Desert, CA 92211 14.0 kw DC, 12.612 kw AC 35 Q.PEAK DUO BLK ML-G10+ 400 35 IQ8A-72-2-US Square D Shingle IronRidge 3/25/23 Size: Modules: Inverter: AC Dis.: Roof: Racking: Date: RD Winkle Co PO Box 470 Thousand Palms, CA 92276 760-272-0003 CA License #688062 C46, C39 Meter Main Service Panel AC Disconnect ON OFF WARNING DUAL POWER SUPPLY SOURCES: UTILITY GRID AND PV SOLAR ELECTRIC SYSTEM NOTE: A directory placard showing the locations of Main Service Disconnect, Photovoltaic Disconnect(s) and Solar Array(s) will be installed. Typical Typical at Backfed Typical AC DISCONNECT Note: Materials used for all marking shall be reflective, weather resistant and suitable for the environment. All letters shall be a minimum height of 3/8", capitalized and white on a red background. On Ext. and Int. Conduit Every 10 Feet and within 1' of turns and within 1' above/or below penetrations and all Disconnects, Combiners and Junction Boxes. Typical WARNING: PHOTOVOLTAIC POWER SOURCE WARNING INVERTER OUTPUT CONNECTION DO NOT RELOCATE THIS OVERCURRENT DEVICE WARNING ELECTRIC SHOCK HAZARD DO NOT TOUCH TERMINALS. TERMINALS ON BOTH THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION. IF A GROUND FAULT IS INDICATED ALL NORMALLY GROUNDED CONDUCTORS MAY BE UNGROUNDED AND ENERGIZED AC Combiner PHOTOVOLTAIC SYSTEM COMBINER PANEL DO NOT ADD LOADS WARNING: PHOTOVOLTAIC POWER SOURCE Typical If Required PHOTOVOLTAIC SYSTEM AC DISCONNECT OPERATING CURRENT 50.75 AMPS OPERATING VOLTAGE 240 VOLTS Typical Typical Typical SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUTDOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN ARRAY SOLAR ELECTRIC PV PANELS Drawing Number: 7 System Labels POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN: CAUTION: SERVICE POINT AND UTILITY METERING PV SYSTEM DISCONNECT FOR UTILITY OPERATION SOLAR PHOTOVOLTAIC ON ROOF IQ8 Series Microinverters Our newest IQ8 Microinverters are the industry’s rst microgrid-forming, software- dened microinverters with split-phase power conversion capability to convert DC power to AC power eciently. The brain of the semiconductor-based microinverter is our proprietary application-specic integrated circuit (ASIC) which enables the microinverter to operate in grid-tied or o-grid modes. This chip is built in advanced 55nm technology with high speed digital logic and has super-fast response times to changing loads and grid events, alleviating constraints on battery sizing for home energy systems. Part of the Enphase Energy System, IQ8 Series Microinverters integrate with the Enphase IQ Battery, Enphase IQ Gateway, and the Enphase App monitoring and analysis software. IQ8 Series Microinverters redene reliability standards with more than one million cumulative hours of power-on testing, enabling an industry- leading limited warranty of up to 25 years. Connect PV modules quickly and easily to IQ8 Series Microinverters using the included Q-DCC-2 adapter cable with plug-n-play MC4 connectors. IQ8 Series Microinverters are UL Listed as PVRapid Shut Down Equipment and conform with various regulations, when installed according to manufacturer’s instructions. Easy to install • Lightweight and compact with plug-n-play connectors • Power Line Communication (PLC) between components • Faster installation with simple two-wire cabling High productivity and reliability • Produce power even when the grid is down* • More than one million cumulative hours of testing • Class II double-insulated enclosure • Optimized for the latest high- powered PV modules Microgrid-forming • Complies with the latest advanced grid support** • Remote automatic updates for the latest grid requirements • Congurable to support a wide range of grid proles • Meets CA Rule 21 (UL 1741-SA) requirements © 2022 Enphase Energy. All rights reserved. Enphase, the Enphase logo, IQ8 Microinverters, and other names are trademarks of Enphase Energy, Inc. Data subject to change. IQ8SE-DS-0001-01-EN-US-2022-03-17 * Only when installed with IQ System Controller 2, meets UL 1741. IQ8H-208V operates only in grid-tied mode. ** IQ8 Series Microinverters supports split phase, 240V. IQ8H-208 supports split phase, 208V only. DATA SHEET (1) The IQ8H-208 variant will be operating in grid-tied mode only at 208V AC. (2) No enforced DC/AC ratio. See the compatibility calculator at https://link.enphase.com/module-compatibility (3) Maximum continuous input DC current is 10.6A (4) Nominal voltage range can be extended beyond nominal if required by the utility. (5) Limits may vary. Refer to local requirements to dene the number of microinverters per branch in your area. IQ8 Series Microinverters INPUT DATA (DC)IQ8-60-2-US IQ8PLUS-72-2-US IQ8M-72-2-US IQ8A-72-2-US IQ8H-240-72-2-US IQ8H-208-72-2-US1 Commonly used module pairings2 W 235 – 350 235 – 440 260 – 460 295 – 500 320 – 540+295 – 500+ Module compatibility 60-cell/120 half-cell 60-cell/120 half-cell, 66-cell/132 half-cell and 72-cell/144 half-cell MPPT voltage range V 27 – 37 29 – 45 33 – 45 36 – 45 38 – 45 38 – 45 Operating range V 25 – 48 25 – 58 Min/max start voltage V 30 / 48 30 / 58 Max input DC voltage V 50 60 Max DC current3 [module Isc] A 15 Overvoltage class DC port II DC port backfeed current mA 0 PV array conguration 1x1 Ungrounded array; No additional DC side protection required; AC side protection requires max 20A per branch circuit OUTPUT DATA (AC)IQ8-60-2-US IQ8PLUS-72-2-US IQ8M-72-2-US IQ8A-72-2-US IQ8H-240-72-2-US IQ8H-208-72-2-US1 Peak output power VA 245 300 330 366 384 366 Max continuous output power VA 240 290 325 349 380 360 Nominal (L-L) voltage/range4 V 240 / 211 – 264 208 / 183 – 250 Max continuous output current A 1.0 1.21 1.35 1.45 1.58 1.73 Nominal frequency Hz 60 Extended frequency range Hz 50 – 68 AC short circuit fault current over 3 cycles Arms 2 4.4 Max units per 20 A (L-L) branch circuit5 16 13 11 11 10 9 Total harmonic distortion <5% Overvoltage class AC port III AC port backfeed current mA 30 Power factor setting 1.0 Grid-tied power factor (adjustable)0.85 leading – 0.85 lagging Peak eciency %97.5 97.6 97.6 97.6 97.6 97.4 CEC weighted eciency %97 97 97 97.5 97 97 Night-time power consumption mW 60 MECHANICAL DATA Ambient temperature range -40ºC to +60ºC (-40ºF to +140ºF) Relative humidity range 4% to 100% (condensing) DC Connector type MC4 Dimensions (HxWxD)212 mm (8.3”) x 175 mm (6.9”) x 30.2 mm (1.2”) Weight 1.08 kg (2.38 lbs) Cooling Natural convection – no fans Approved for wet locations Yes Pollution degree PD3 Enclosure Class II double-insulated, corrosion resistant polymeric enclosure Environ. category / UV exposure rating NEMA Type 6 / outdoor COMPLIANCE Certications CA Rule 21 (UL 1741-SA), UL 62109-1, UL1741/IEEE1547, FCC Part 15 Class B, ICES-0003 Class B, CAN/CSA-C22.2 NO. 107.1-01 This product is UL Listed as PV Rapid Shut Down Equipment and conforms with NEC 2014, NEC 2017, and NEC 2020 section 690.12 and C22.1-2018 Rule 64-218 Rapid Shutdown of PV Systems, for AC and DC conductors, when installed according to manufacturer’s instructions. IQ8SE-DS-0001-01-EN-US-2022-03-17 Roof Mount System Strongest Rails Longer spans between attachments, fewer roof penetrations. 6+)KXZO࠭KJ Pre-stamped engineering letters available in most states. Simple Assembly Versatile and adjustable components simplify any array design. Design Software Online tool generates a complete bill of materials in minutes. /TZKMXGZKJ-XU[TJOTM UL 2703 system eliminates separate module grounding components. 20 Year Warranty Twice the protection offered by competitors. ([ORZLUXYURGX۱YZU[MNKYZXUULY Anchored by the strongest rails in solar, the IronRidge Roof Mount System provides the durability and versatility to handle virtually any residential or commercial rooftop. 7KHXQLTXHFXUYHGSURߑOHRIWKH;565DLOLQFUHDVHVLWVVWUHQJWKZKLOHDOVRJLYLQJLWDQDWWUDFWLYHORRNPDNLQJ LWYHU\FXVWRPHUIULHQGO\,QDGGLWLRQ,URQ5LGJH5DLOVDUHFHUWLߑHGIRULQWHJUDWHGJURXQGLQJZKLFKHOLPLQDWHV VHSDUDWHPRGXOHJURXQGLQJFRPSRQHQWVDQGSURFHGXUHVPDNLQJLWYHU\LQVWDOOHUIULHQGO\ *GZGYNKKZ Online Software The IronRidge Design Assistant helps you go from rough layout to fully engineered system. For free. -UZUOXUTXOJMKIUSXS n/XUT8OJMK/TI'RRXOMNZYXKYKX\KJ<OYOZ]]]OXUTXOJMKIUSUXIGRRLUXSUXKOTLUXSGZOUT<KXYOUT Rails 9ZGTJXGXJ8GORY>892OMNZ8GORY>828GOR9VROIKY Curved rails increase spanning capabilities and aesthetics. • $YDLODEOHLQFOHDUDQGEODFNDQRG • Multiple sizes between 12’ and 18’ • Made of corrosion resistant alum. 'ZZGINSKTZY ,RGYNOTMY 'JP[YZGHRK2,KKZ Tilt Leg Kits Lightweight rails reduce cost for lighter load conditions. • $YDLODEOHLQFOHDUDQGEODFNDQRG • Multiple sizes between 12’ and 18’ • Made of corrosion resistant alum. Internal splices seamlessly connect rails, allowing easy L-foot installation. • 'LIIHUHQWYHUVLRQVIRU;56DQG;5/ • Includes self-tapping screws • Available with grounding straps FlashFoot™ is an all-in-one mounting product for composition shingle roofs. • Integrated L-Foot and hardware ڞ&HUWLߑHGFRPSOLDQWZLWK,%& ,5& ڞ3(FHUWLߑHGZLWK,URQ5LGJH5DLOV Slotted L-feet provide adaptable DWWDFKPHQWWRVWDQGRIIVDQGߒDVKLQJV • $YDLODEOHLQFOHDUDQGEODFNDQRG ڞ:RUNVZLWK;56DQG;5/UDLOV • Compatible with third-party parts Fixed and adjustable tilt legs allow adjustment in all three axes. • $WWDFKHVGLUHFWO\WR;56DQG;5/ • Ships with all required hardware • Multiple sizes for 5-45 deg. tilts )RGSVY 'IIKYYUXOKY +TJ)RGSVY Secure modules to the end of the rails. • &OHDUDQGEODFNDQRG • Sizes from 1.22” to 2.3” • Optional bottom clamps 3OJ)RGSVY Fasten modules in the middle of the rails. • &OHDUDQGEODFNDQRG • T-bolt or hex nut designs • Grounding clamp offered +TJ)GVY 3URYLGHDߑQLVKHGORRNIRU rails. • Keeps out debris ڞ%ODFNSRO\FDUERQDWH • UV protected Wire Clips Organize both DC and AC wiring along the rails. • Attaches to both rails • Supports ten 5mm wires • UV protected MacBook Pro '\GORGHRK]OZN/TZKMXGZKJ-XU[TJOTM ,URQ5LGJHRIIHUV8/FHUWLߑHG components that automatically bond modules and rails to ground. -UZUOXUTXOJMKIUSOM *GZGYNKKZ Tech Brief Class A Fire Rating Background $OOURRߔQJSURGXFWVDUHWHVWHGDQG FODVVLߔHGIRUWKHLUDELOLW\WRUHVLVWߔUH 5HFHQWO\WKHVHߔUHUHVLVWDQFHVWDQGDUGV ZHUHH[SDQGHGWRLQFOXGHVRODUHTXLSPHQW DVSDUWRIWKHURRIV\VWHP6SHFLߔFDOO\WKLV UHTXLUHVWKHPRGXOHVPRXQWLQJKDUGZDUH DQGURRIFRYHULQJWREHWHVWHGWRJHWKHUDV DV\VWHPWRHQVXUHWKH\DFKLHYHWKHVDPH ߔUHUDWLQJDVWKHRULJLQDOURRIFRYHULQJ $GRSWLRQRIWKHVHQHZUHTXLUHPHQWVZLOO EHJLQLQ&DOLIRUQLDLQDQGH[WHQGWR WKHUHVWRIWKHFRXQWU\LQ /XUT8OJMK)KXZOߟIGZOUT ,Q$XJXVW,URQ5LGJHZDVWKHߔUVW FRPSDQ\WRUHFHLYHD&ODVV$)LUH5DWLQJڐ WKHKLJKHVWSRVVLEOHUDWLQJڐIURP,QWHUWHN *URXSSOFD1DWLRQDOO\5HFRJQL]HG7HVWLQJ /DERUDWRU\ ,URQ5LGJH5RRI0RXQWSURGXFWVZHUHWHVWHG RQߕDWDQGVORSHGURRIVLQDFFRUGDQFHZLWK WKHQHZ8/ 8/WHVWVWDQGDUGV 7KHWHVWLQJHYDOXDWHGWKHV\VWHPڕVDELOLW\WR UHVLVWߕDPHVSUHDGEXUQLQJPDWHULDODQG VWUXFWXUDOGDPDJHWRWKHURRI 5HIHUWRWKHWDEOHEHORZWRGHWHUPLQHWKH UHTXLUHPHQWVIRUDFKLHYLQJD&ODVV$)LUH 5DWLQJRQ\RXUQH[WSURMHFW Test Setup Solar Modules 6RODUPRGXOHVDUHJLYHQD7\SH FODVVLߔFDWLRQEDVHGRQWKHLU PDWHULDOVDQGFRQVWUXFWLRQ Mounting System 0RXQWLQJLVWHVWHGDVSDUWRID V\VWHPWKDWLQFOXGHVW\SHWHVWHG PRGXOHVDQGߔUHUDWHGURRIFRYHULQJ Roof Covering 5RRIFRYHULQJSURGXFWVDUHJLYHQD )LUH&ODVV5DWLQJRI$%RU&EDVHG RQWKHLUWHVWHGߔUHUHVLVWDQFH $EXUQLQJZRRGHQEORFNLVSODFHGRQPRGXOHDVDIDQEORZVDWPSK )ODPHFDQQRWEHVHHQRQXQGHUVLGHRIURRIZLWKLQPLQXWHV Burning Brand Test )ODPHDWVRXWKHUQHGJHRIURRILVDLPHGXSWKHURRIDVDIDQEORZVDW PSK7KHߕDPHFDQQRWVSUHDGIHHWRUPRUHLQPLQXWHV Spread of Flame Test Fire Testing Process Roof Slope Mount Module Fire Rating* 6WHHS6ORSH  ݭGHJUHHV )OXVK 7\SH Class A 7LOW 7\SH Class A /RZ6ORSH GHJUHHV )OXVK 7\SH Class A 7LOW 7\SH Class A &ODVV$UDWHG39V\VWHPVFDQEHLQVWDOOHGRQ&ODVV$%DQG&URRIV Tech Brief © 2015 IronRidge, Inc. All rights reserved. Visit www.ironridge.com or call 1-800-227-9523 for more information. Version 1.12 More Resources ,OXK8GZOTM)KXZOߟIGZK 9LVLWRXUZHEVLWHWRGRZQORDGWKHRIߔFLDO8/ FHUWLߔFDWLRQGRFXPHQW Go to IronRidge.com +TMOTKKXOTM)KXZOߟIGZOUT2KZZKXY :HRIIHUFRPSOHWHHQJLQHHULQJUHVRXUFHV DQGSUHVWDPSHGFHUWLߔFDWLRQOHWWHUV Go to IronRidge.com Frequently Asked Questions What is a “module type”? 7KHQHZ8/VWDQGDUGLQWURGXFHVWKHFRQFHSWRID 39PRGXOHW\SHEDVHGRQFRQVWUXFWLRQSDUDPHWHUV DQGߔUHSHUIRUPDQFHSDUDPHWHUV7KHSXUSRVHRI WKLVFODVVLߔFDWLRQLVWRFHUWLI\PRXQWLQJV\VWHPVZLWKRXW QHHGLQJWRWHVWLWZLWKHYHU\PRGXOH =NGZXUUߟTMSGZKXOGRYGXKIU\KXKJ% $OOߔUHUDWHGURRߔQJPDWHULDOVDUHFRYHUHGZLWKLQWKLV FHUWLߔFDWLRQLQFOXGLQJFRPSRVLWLRQVKLQJOHFOD\DQG FHPHQWWLOHPHWDODQGPHPEUDQHURRIV What if I have a Class C roof, but the jurisdiction now requires Class A or B? *HQHUDOO\ROGHUURRIVZLOOW\SLFDOO\EHژJUDQGIDWKHUHG LQڙDQGZLOOQRWUHTXLUHUHURRߔQJ+RZHYHULIRU PRUHRIWKHURRߔQJPDWHULDOLVUHSODFHGIRUWKHVRODU LQVWDOODWLRQWKHFRGHUHTXLUHPHQWZLOOEHHQIRUFHG =NKXKOYZNKTK]ߟXKXGZOTMXKW[OXKSKTZIUJKROYZKJ% ,%&)LUHFODVVLߔFDWLRQ5RRIWRS PRXQWHGSKRWRYROWDLFV\VWHPVVKDOOKDYHWKHVDPHߔUH FODVVLߔFDWLRQDVWKHURRIDVVHPEO\UHTXLUHGE\6HFWLRQ  Where is a Class A Fire Rating required? 7KHJHQHUDOUHTXLUHPHQWIRUURRߔQJV\VWHPVLQWKH,%& UHIHUVWRD&ODVV&ߔUHUDWLQJ&ODVV$RU%LVUHTXLUHGIRU DUHDVVXFKDV:LOGODQG8UEDQ,QWHUIDFHDUHDV :8, DQG IRUYHU\KLJKߔUHVHYHULW\DUHDV0DQ\RIWKHVHDUHDVDUH IRXQGWKURXJKRXWWKHZHVWHUQ8QLWHG6WDWHV&DOLIRUQLD KDVWKHPRVW&ODVV$DQG%URRIߔUHUDWLQJUHTXLUHPHQWV GXHWRZLOGߔUHFRQFHUQV Are standard mid clamps covered? 0LGFODPSVDQGHQGFODPSVDUHFRQVLGHUHGSDUWRIWKH 39ژV\VWHPڙDQGDUHFRYHUHGLQWKHFHUWLߔFDWLRQ =NGZGZZGINSKTZYGTJߠGYNOTMYGXKJKKSKJ compatible with Class A? $WWDFKPHQWVDQGWKHLUUHVSHFWLYHߕDVKLQJVDUHQRW FRQVWLWXHQWVRIWKHUDWLQJDWWKLVWLPH$OOFRGHFRPSOLDQW ߕDVKLQJPHWKRGVDUHDFFHSWDEOHIURPDߔUHUDWLQJ VWDQGSRLQW What mounting height is acceptable? 8/ߔUHWHVWLQJZDVSHUIRUPHGZLWKDJDSRIڙZKLFKLV FRQVLGHUHGZRUVWFDVHLQWKHVWDQGDUG7KHUHIRUHWKH UDWLQJLVDSSOLFDEOHWRDQ\PRGXOHWRURRIJDS 'S/XKW[OXKJZUOTYZGRRYQOXZOTMZUSKKZZNKߟXK code? 1R,URQ5LGJHDFKLHYHGD&ODVV$ߔUHUDWLQJZLWKRXWDQ\ DGGLWLRQDOUDFNLQJFRPSRQHQWV =NGZJKZKXSOTKY,OXK)RGYYOߟIGZOUT% )LUH&ODVVLߔFDWLRQUHIHUVWRDߔUHUHVLVWDQFHUDWLQJ V\VWHPIRUURRIFRYHULQJPDWHULDOVEDVHGRQWKHLUDELOLW\ WRZLWKVWDQGߔUHH[SRVXUH &ODVV$HIIHFWLYHDJDLQVWVHYHUHߔUHH[SRVXUH &ODVV%HIIHFWLYHDJDLQVWPRGHUDWHߔUHH[SRVXUH &ODVV&HIIHFWLYHDJDLQVWOLJKWߔUHH[SRVXUH What if the roof covering is not Class A rated? 7KH,URQ5LGJH&ODVV$UDWLQJZLOOQRWGLPLQLVKWKHߔUH UDWLQJRIWKHURRIZKHWKHU&ODVV$%RU& =NGZZORZYOYZNKZORZSU[TZY_YZKSߟXKXGZKJLUX% 7KHWLOWPRXQWV\VWHPLVUDWHGIRUGHJUHHVDQGXSDQG DQ\URRIWRPRGXOHJDSRUPRXQWLQJKHLJKW AUTHORIZATION TO MARK Applicant:Manufacturer: Address:Address: Country:Country: Contact:Contact: Phone:Phone: FAX:FAX: Email:Email: Standard(s): Product: Brand Name: Models: This Authorization to Mark is for the exclusive use of Intertek's Client and is provided pursuant to the Certification agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this Authorization to Mark. Only the Client is authorized to permit copying or distribution of this Authorization to Mark and then only in its entirety. Use of Intertek’s Certification mark is restricted to the conditions laid out in the agreement and in this Authorization to Mark. Any further use of the Intertek name for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. Initial Factory Assessments and Follow up Services are for the purpose of assuring appropriate usage of the Certification mark in accordance with the agreement, they are not for the purposes of production quality control and do not relieve the Client of their obligations in this respect. Intertek Testing Services NA Inc. 545 East Algonquin Road, Arlington Heights, IL 60005 Telephone 800-345-3851 or 847-439-5667 Fax 312-283-1672 UL Subject 2703 Outline of Investigation for Rack Mounting Systems and Clamping Devices for Flat-Plate Photovoltaic Modules and Panels, Issue Number: 1, October 4, 2010 XR Rails with Integrated Grounding. XR Rails IronRidge Roof Mount Control Number:4007559 Authorized by: for Thomas J. Patterson, Certification Manager This document supersedes all previous Authorizations to Mark for the noted Report Number. yschwarz@ironridge.com jnorsworthy@ironridge.com Party Authorized To Apply Mark:Same as Manufacturer Report Issuing Office:Lake Forest, CA Yann Schwarz Jim Norsworthy (800) 227-9523 (800) 227-9523 (707) 459-1833 (707) 459-1833 IronRidge, Inc.IronRidge, Inc. 1495 Zephyr Ave Hayward, CA 94544 1435 Baechtel Road Willits, CA 95490 USA USA This authorizes the application of the Certification Mark(s) shown below to the models described in the Product(s) Covered section when made in accordance with the conditions set forth in the Certification Agreement and Listing Report. This authorization also applies to multiple listee model(s) identified on the correlation page of the Listing Report. This document is the property of Intertek Testing Services and is not transferable. The certification mark(s) may be applied only at the location of the Party Authorized To Apply Mark. Page 1 of 3 ATM for Report 101541132LAX-002 ATM Issued: 24-Apr-2015 ED 16.3.15 (1-Jan-13) Mandatory AUTHORIZATION TO MARK Applicant:Manufacturer: Address:Address: Country:Country: Contact:Contact: Phone:Phone: FAX:FAX: Email:Email: Standard(s): Product: Brand Name: Models:XR Rails This Authorization to Mark is for the exclusive use of Intertek's Client and is provided pursuant to the Certification agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this Authorization to Mark. Only the Client is authorized to permit copying or distribution of this Authorization to Mark and then only in its entirety. Use of Intertek’s Certification mark is restricted to the conditions laid out in the agreement and in this Authorization to Mark. Any further use of the Intertek name for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. Initial Factory Assessments and Follow up Services are for the purpose of assuring appropriate usage of the Certification mark in accordance with the agreement, they are not for the purposes of production quality control and do not relieve the Client of their obligations in this respect. Intertek Testing Services NA Inc. 545 East Algonquin Road, Arlington Heights, IL 60005 Telephone 800-345-3851 or 847-439-5667 Fax 312-283-1672 UL Subject 2703 Outline of Investigation for Rack Mounting Systems and Clamping Devices for Flat-Plate Photovoltaic Modules and Panels, Issue Number: 1, October 4, 2010 XR Rails with Integrated Grounding. IronRidge Roof Mount Control Number:4008377 Authorized by: for Thomas J. Patterson, Certification Manager This document supersedes all previous Authorizations to Mark for the noted Report Number. yschwarz@ironridge.com jnorsworthy@ironridge.com Party Authorized To Apply Mark:Same as Manufacturer Report Issuing Office:Lake Forest, CA Yann Schwarz Jim Norsworthy Or Dave Taggart (800) 227-9523 (707) 363-3025 (707) 459-1833 (510) 225-0975 IronRidge, Inc.IronRidge, Inc. 1495 Zephyr Ave Hayward, CA 94544 1495 Zephyr Ave Hayward, CA 94544 USA USA This authorizes the application of the Certification Mark(s) shown below to the models described in the Product(s) Covered section when made in accordance with the conditions set forth in the Certification Agreement and Listing Report. This authorization also applies to multiple listee model(s) identified on the correlation page of the Listing Report. This document is the property of Intertek Testing Services and is not transferable. The certification mark(s) may be applied only at the location of the Party Authorized To Apply Mark. Page 2 of 3 ATM for Report 101541132LAX-002 ATM Issued: 24-Apr-2015 ED 16.3.15 (1-Jan-13) Mandatory AUTHORIZATION TO MARK Applicant:Manufacturer: Address:Address: Country:Country: Contact:Contact: Phone:Phone: FAX:FAX: Email:Email: Standard(s): Product: Brand Name: Models: XR Rails with Integrated Grounding. IronRidge Roof Mount XR Rails for Thomas J. Patterson, Certification Manager This document supersedes all previous Authorizations to Mark for the noted Report Number. This Authorization to Mark is for the exclusive use of Intertek's Client and is provided pursuant to the Certification agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this Authorization to Mark. Only the Client is authorized to permit copying or distribution of this Authorization to Mark and then only in its entirety. Use of Intertek’s Certification mark is restricted to the conditions laid out in the agreement and in this Authorization to Mark. Any further use of the Intertek name for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. Initial Factory Assessments and Follow up Services are for the purpose of assuring appropriate usage of the Certification mark in accordance with the agreement, they are not for the purposes of production quality control and do not relieve the Client of their obligations in this respect. Intertek Testing Services NA Inc. 545 East Algonquin Road, Arlington Heights, IL 60005 Telephone 800-345-3851 or 847-439-5667 Fax 312-283-1672 UL Subject 2703 Outline of Investigation for Rack Mounting Systems and Clamping Devices for Flat-Plate Photovoltaic Modules and Panels, Issue Number: 1, October 4, 2010 Party Authorized To Apply Mark:Same as Manufacturer Report Issuing Office:Lake Forest, CA Control Number:4008083 Authorized by: (800) 227-9523 (480) 967-2038 (707) 459-1833 (480) 829-0838 yschwarz@ironridge.com andy@precisiondie.com IronRidge, Inc.Precision Die & Stamping, Inc. 1495 Zephyr Ave Hayward, CA 94544 1704 W. 10th Street Tempe, AZ 85281 USA USA Yann Schwarz Andy Frola This authorizes the application of the Certification Mark(s) shown below to the models described in the Product(s) Covered section when made in accordance with the conditions set forth in the Certification Agreement and Listing Report. This authorization also applies to multiple listee model(s) identified on the correlation page of the Listing Report. This document is the property of Intertek Testing Services and is not transferable. The certification mark(s) may be applied only at the location of the Party Authorized To Apply Mark. Page 3 of 3 ATM for Report 101541132LAX-002 ATM Issued: 24-Apr-2015 ED 16.3.15 (1-Jan-13) Mandatory Tech Brief Moving Flashing Forward :HVHWRXWWRGHVLJQDÁDVKLQJWKDWFKHFNHGDOO WKHER[HVIXOO\ZDWHUSURRIIDVWDQGHDV\WRLQVWDOO FRUUHFWO\HFRQRPLFDODQGVWURQJHQRXJKWRKDQGOH HYHU\HQYLURQPHQWDOFRQGLWLRQ)ODVK9XHGRHVLWDOO 7KHRSWLPL]HGÁDVKLQJGHVLJQIHDWXUHVDODUJH YLHZSRUWIRUHDV\DOLJQPHQWZLWKWKHSLORWKROH$QG WKH*ULS&DSDQG*ULS&DSVLWVQXJO\LQSODFHVR WKHODJFDQEHGULYHQVLQJOHKDQGHGO\ )ODVK9XHŒ GripCap & GripCap+ 7KHžFDSDEOH*ULS&DS µ WDOO DQG*ULS&DS µWDOO FDQEH SODFHGLQDQ\RULHQWDWLRQDQGSURYLGHD ´IULFWLRQÀWµIRUHDV\LQVWDOOV3XVKVQXJ LQWRWKHYLHZSRUWZLWKRXWZRUU\LQJLWZLOO UROODZD\RUURWDWHZKLOHGULYLQJWKHODJ Three-Tier Water Seal, Reimagined )ODVK9XH·VVHDODUFKLWHFWXUHXWLOL]HVWKUHHOD\HUV RISURWHFWLRQ7KHYLHZSRUWLVHOHYDWHGµDQG SURYLGHVD´IULFWLRQÀWµIRUWKH*ULS&DS7KH*ULS&DS IXOO\FRYHUVWKHYLHZSRUWZKLOHDVHDOLQJZDVKHU DGGVDQRWKHUOD\HURISURWHFWLRQ$QGDQ(3'0 ZDVKHUDQGODJEROW´VHDOWKHGHDOµLQWKHVWDFN Large Viewport in Flashing 7KHODUJHYLHZSRUWPDNHVLWHDV\WR DOLJQWKHÁDVKLQJZLWKWKHSLORWKROHDQG GULYHWKHODJFHQWHUHGLQWRWKHUDIWHU7KH HOHYDWHGULPQRWRQO\SURYLGHVDVWXUG\ GRFNIRUWKH*ULS&DSRU*ULS&DSEXW LQFUHDVHVZDWHUVKHGGLQJFDSDELOLWLHV ฦµ 7ULSOH&HUWLÀHGWR 3URWHFWWKH5RRI™ 8/  7$6 $  © 2020 IronRidge, Inc. All rights reserved. Visit www.ironridge.com or call 1-800-227-9523 for more information. Version 1.0 Tech Brief Solve Roof Undulations See Your Pilot Holes Also Available: GripCap+ :HNQRZURRIVDUHQRWDOZD\V SHUIHFWO\ÁDW*ULS&DSFDQKHOS ZKHQXQGXODWLRQVJHWLQWKHZD\ Large Viewport in Flashing )ODVK9XHPDNHVSLORWKROHVKLJKO\ YLVLEOHOLNHQHYHUEHIRUH1RPRUH WHGLRXVJXHVVZRUNRQKRWURRIV ;Y\Z[LK:[YLUN[O *LY[PÄJH[PVU $WWDFKPHQW/RDGLQJ )ODVK9XHKDVEHHQWHVWHGDQGUDWHGWRVXSSRUW OEV RIXSOLIWDQG OEV RIODWHUDOORDG 6WUXFWXUDO&HUWLÀFDWLRQ 'HVLJQHGDQGFHUWLÀHGIRUFRPSOLDQFHZLWKWKH,QWHUQDWLRQDO%XLOGLQJ&RGH $6&(6(, :DWHU6HDO5DWLQJV 3DVVHGERWKWKH8/6HFWLRQ´5DLQ7HVWµDQG7$6´:LQG'ULYHQ5DLQ7HVWµE\,QWHUWHN 8//LVWHG6\VWHP &RQIRUPVWR8/PHFKDQLFDODQGERQGLQJUHTXLUHPHQWV6HH)OXVK0RXQW0DQXDOIRUPRUHLQIR Cut Sheet FlashVue v1.0 1 2 3 4 .61 7/16" Head 4.25 .26 5/16 THD 1) BOLT, LAG 5/16 x 4.25" FLASHVUE ITEM NO DESCRIPTION QTY IN KIT 1 BOLT, LAG 5/16 X 4.25"1 2 WASHER, EPDM BACKED 1 3 FM FLASHING, MILL OR BLACK 1 4 GRIP CAP, MILL OR BLACK 1 PART NUMBER DESCRIPTION FV-01-M1 FLASHING, FLASHFOOT, MILL FV-01-B1 FLASHING, FLASHFOOT, BLACK Property Value Material 300 Series Stainless Steel Finish Clear Cut Sheet v1.0