HomeMy WebLinkAboutRevision Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1 .310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
Structural Calculations for a Roof Mounted Solar Photovoltaic System for:
Chris Berg QRO\N. 1 y9l
74320 Aster Dr 6 Q)
LU
Palm Desert, CA 92260 No. C58724
Exp.3-31-25
Applicable Codes: w
�T9'FOFcA_\F
2022 California Building Code, 2022 California Electric Code,
2022 California Mechanical Code, American Society of Civil Engineers
Standard ASCE 7-16 Minimum Design Loads for Buildings and Other
Structures, American Wood Council 2018 National Design Specification
for Wood Construction, Local Municipal Code, and all other codes which
are adopted by reference or enacted by law.
Assumed Design Parameters:
The existing structure has been built under a building permit and is in its
original condition. The existing roof structure is capable of its code
required live load and the ability of the roof structure to support live loads
has not been substantially reduced by the age of the structure, termites or
mold, or unauthorized modifications to the existing structure. Solar Energy
Contractor shall make an inspection of the existing roof framing system
prior to installation of the roof mounted solar energy system to verify that
the existing roof is capable of supporting minimum roof live loads.
Assumed Design Parameters:
All 2x members are grade Douglas Fir #2 or better
All 4X members are grade Douglas Fir #1 or better
All Roof Connectors are Simpson Strong-Tie or Equal
All Concrete Foundations are f'c = 2500 psi or stronger
Original Structure was built to the Type-V Wood Framed Standards of the
Applicable Building Code at the time of Construction.
Sht # 1 of 7
2023-4735 Vision CE Chris Berg September 6, 2023
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1 .310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
Note to Building Official:
Based upon a review of the proposed plans I am confident that the
existing roof framing system is capable of safely supporting the additional
loads caused by the new solar photovoltaic energy system. The contractor
shall field verify that the existing roof structure is in its original permited
condition and verify that it can support the normal code required roof live
loads. Attached in this package are several calculations showing that the
roof members can support the additional weight of the solar array.
Furthermore, an analysis of the solar array's support for wind forces and a
seismic analysis of the existing structure are also included.
Check Existing 2X6 Roof Rafters (D- 16" O.C.:
(Assume max rafter span = 11 .75 ft.)
W DL+ LL
I I
w = 30 psf x 1 .33 ft. = 39.9 plf R1 R2
11.75'
�oQ�OF ESS/04//
W.
Total load on rafters = 39.9 plf x 11 .75 ft. = 469 Ibs U m
Of No. C58724
Exp.3-31-25
��9TF I OF C AL FO��\P
Sht # 2of7
2023-4735 Vision CE Chris Berg September 6, 2023
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1 .310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
Check Existing 2X6 Roof Rafters (cb- 16" O.C.:
P P P P
WLLIIIIIIIIIIIIIIH6 6 b b
W DL
WDL+ LL = 30 psf x 1 .33 ft. = 39.9 plf
WDL = 14 psf x 1 .33 ft. = 18.6 plf R1 R2
11.75'
3' 3.4' 1.5' 3.4' 0.45
Total load on rafters = ( 39.9 plf x4.95ft ) + ( 18.6 plf x6.8ft ) + ( 5.33' x1 .7' x3 psf x4 )
= 433 Ibs < 469 Ibs OK
Check attachment of Support to Existing Structure for Wind Uplift
CHECK SOLAR STRUCTURE ATTACHMENTS PER ASCE 7-16 WIND LOADS ON BUILDING
APPURTENANCES AND OTHER STRUCTURES Section 29.4.4 THEREFORE CHECK
ATTACHMENT FOR TYPICAL CRITICAL LOAD WHICH IS THE EDGE ZONE - ZONE 2.
NOTE: PER DEFINITION ON SHEETS 246 & 247 OF ASCE 7-16 EFFECTIVE WIND AREA:
FOR ROOFTOP SOLAR ARRAYS, THE EFFECTIVE WIND AREA IN FIG. 29.4-7 IS
EQUAL TO THE TRIBUTARY AREA FOR THE STRUCTURAL ELEMENT BEING
CONSIDERED, EXCEPT THAT THE WIDTH OF THE EFFECTIVE WIND AREA NEED NOT
BE LESS THAN ONE-THIRD ITS LENGTH. �OQRpFESS/olv
W. 114
EFFECTIVE AREA = 15 SQ FT w o M
No. C58724
Exp. 3-31-25
LPT9rF OF l CAL\F���\P
Sht # 3of7
2023-4735 Vision CE Chris Berg September 6, 2023
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1 .310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
Check attachment of Support to Existing Structure for Wind Uplift - Cont'd
Tributary Area to Each Solar Mount = 6 ft. x 3.15 ft. = 18.9 sq. ft. ( Max )
Calculate Design Wind Pressure at each support (Wind Speed 130 mph Exposure C):
p = q h (GCp)(YE)(Y J Eq'n 29.4-7 ASCE 7-16
qh = 0.00256KZ KZt Kd Ke V2 Eq'n 26.10-1 ASCE 7-16
Note:
KZ = velocity pressure coefficient Section 29.10.1 ASCE 7-16
KZ = 0.9 (Exposure C, Height = 20 ft or less)
KZt = Topographical Factor = 1 .0 oQROFEsSIOli,1
Kd = Wind Directionality Factor = 0.85 114
CO o
Ke = Ground Elevation Factor = 1 .0Of No. C58724
V = 130 mph ; VASB = 101 mph * Exp.3-31-25
qh = 0.00256 (0.9) (1 .0) (0.85) (1 .0) (101)2 cj�x civic �Q
q h = 19.98 psf 9�F OF C
GCp = -2.0 (Zone 2 ; Effective Area = 15 sq. ft. )
Y E = Exposure Factor = 1 .5
Ya = Solar Array Pressure Equalization Factor = 0.7 Fig. 29.4-8 ASCE 7-16
p = qh (GC p)(YE)(Ya)
p = 19.98 psf(-2.0) (1.5) (0.7) = 42 psf
Sht # 4of7
2023-4735 Vision CE Chris Berg September 6, 2023
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1 .310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
Check attachment of Support to Existing Structure for Wind Uplift - Cont'd
Nominal (Unfactored) Uplift at each support = 42 psf x 18.9 sq. ft. = 793.8 Ibs
Note: Section 2.4.1 of ASCE 7-16, Basic Load Combinations for Allowable Stress
Design. Note: Applicable Load Combination #5 (D + 0.6W)
Design (Factored) Uplift at each support = 0.6 x 793.8 Ibs = 476 Ibs
Load per lag screw = 476 Ibs / 1 = 476 Ibs
Determine allowable load per 5/16" lag screw w/ 2.5" embedment into wood below
according to the 2018 NDS. �oQROFESSIO4,,
w.
W ' = W x Cd x Ct Table 10.3.1 2018 NDS ' m
�where No. C58724 �
Exp.3-31-25
W = 266 Ibs / in. of embedment per Table 12.2a sT civi\� �P
Cd = 1 .6 per Table 2.3.2 of 2018 NDS 9rFOF Ca��F°��
Ct = 1 .0 per Table 2.3.3 of 2018 NDS
W' = 266 Ibs/ in. x 2.5 in. x 1 .6 x 1 .0 = 1 ,064 Ibs > 476 Ibs OK
Use Support connected to 2x Min. Roof Member w/
(1) 5116" x 3.5" lag screws per connection minimum.
Sht # 5of7
2023-4735 Vision CE Chris Berg September 6, 2023
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1 .310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
Free Body Diagram of Reverse-tilt Sub Array
�oQROF ESSIp�,9l
W.
No. C58724
Exp.3-31-25
`" CIV1 �Q
9TF OF C AL�FO��
Shear Reaction
Uplift Reaction Uplift Reaction
Shear Reaction = (5.33 ft x 6.3 ft x 42 psf x sin 10) = 244.9 Ibs
(Note: Angle between Roof and Panels is 10 degrees)
Allowable lateral Load at 5/16" diameter lag screw w/ 2.5" embedment
Allowable Load = 200 Ibs x 1 .6 x 1 = 320 Ibs > 244.9 Ibs OK
See plans for connection details.
Sht # 5.1 of
2023-4735 Vision CE Chris Berg September 6, 2023
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1 .310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
Check Seismic load due to added dead load of photovoltaic system.
Determine Seismic Weight of Existing Building:
Effective Existing Seismic Weight
Area of (E) Building = Approximately 1 ,700 Sq. ft
Approximate
Effective = 1 ,700 sq. ft. x 30 psf ave. = 51 ,000 LBS
Seismic Weight
�oQROF ESS1049
DETERMINE BASE SHEAR W
No. C58724
V = CS W EQ'N 12.8-1 ASCE 7-16 * Exp.3-31-25
LP�9TF ' AL�FO��\P
CS — S DS EQ'N 12.8-2 ASCE 7-16 OF C
[R]
Ie
R = THE RESPONSE MODIFICATION FACTOR IN TABLE 12.2-1
R = 6.5 WOOD SHEAR WALLS
le = 1 .0 IMPORTANCE FACTOR
SDS = 2/3 X SMS
SMS = FAX SS
SMS = 1 .2x1 .5 = 1 .8
SDS = 2/3 x 1 .8 = 1 .2
CS = SRS = 0.185 EQ'N 12.8-2 ASCE 7-16
LIeJ
Sht # 6of7
2023-4735 Vision CE Chris Berg September 6, 2023
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1 .310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
EXISTING BASE SHEAR
V = 0.185 x 51 ,000 LBS = 9,435 LBS
DETERMINE NEW BASE SHEAR �oQROFESSIO l
w.
Determine Seismic Weight of Building with Solar Array: o �%
No. C58724 70
EXISTING
* Exp.3-31-25
SEISMIC = 51 ,000 LBS
LP
WEIGHT �9TFOF'CAL F���\P
NEW SOLAR
ARRAY = 3 PSF x 31 PANELS x 6.3' x 3.4' = 1 ,993 LBS
NEW
SEISMIC = 51 ,000 LBS + 1 ,993 LBS = 52,993 LBS
WEIGHT
THEREFORE NEW BASE SHEAR:
V = 0.185 x 52,993 = 9,804 LBS EQ'N 12.8-1 ASCE 7-16
% CHANGE = 9,804 LBS - 9,435 LBS , 100 = 3.9 % < 10 % OK
9,435 LBS
OK. PER ASCE 7-16 SECTION 11 B.4 ALTERATIONS
EXISTING LATERAL FORCE RESISTING SYSTEM IS EXEMPT
FROM ANALYSIS SINCE NEW SEISMIC FORCE IS
LESS THAN 10% GREATER THAN EXISTING SEISMIC FORCE
"Alterations may be made to any structure without requiring the existing structure to
comply with this standard, provided that the alterations comply with the requirements for a
new structure. Alterations that increase the seismic force in any existing structural element
by more than 10% or decrease the design strength of any existing structural element to
resist seismic forces by more than 10% shall not be permitted unless the entire seismic
force-resisting system is determined to comply with this standard for a new structure."
End of Calculations
Sht # 7of7
2023-4735 Vision CE Chris Berg September 6, 2023