HomeMy WebLinkAbout_SOLR23-0806_83984PV-Berg Design Plans V1 (Palm Desert)SCOPE OF WORK: INSTALL (31) SILFAB PRIME SIL-400HC+ SOLAR ELECTRIC MODULES AND (31) SOLAREDGE S440 DC POWER OPTIMIZERS ON THE EXISTING 1ST STORY TILE ROOF. INSTALL ASSOCIATED MOUNTING HARDWARE, JUNCTION BOXES, CONDUIT, CONDUCTORS AND GROUNDING. INSTALL (1) SOLAREDGE SE10000H-US INVERTER WITH INTEGRATED DC DISCONNECT, (1) FUSED AC DISCONNECT, AND CONNECT TO SCE INSTALLED GMA. HOMEOWNER:CHRIS BERG PH: 408.510.9153 ADDRESS:74320 ASTER DRIVE PALM DESERT, CA 92260 DATE: 3/24/23 UNDERLINE ENERGY CONCEPTS INC. 18540 PASADENA STREET LAKE ELSINORE, CA 92530 PH: 951.201.1900 JESSE M. MALONE C10 - 1015714 VICINITY MAP BERG RESIDENCE SHEET INDEX: SHEET 1 PROJECT INFO, VICINITY MAP, NOTES, SCOPE OF WORK SHEET 2 SITE/ROOF PLAN, ELEVATION DETAIL SHEET 3 ELECTRIC LINE DRAWING, GROUNDING DETAIL SHEET 4 CALCULATIONS, SIGNS ATTACHED MODULE, INVERTER, MOUNTING HARDWARE SPEC SHEETS STRUCTURAL REPORT NTS SHEET NOTICE: ANY CHANGES TO OR USES OF THESE DOCUMENTS/DRAWINGS WITHOUT THE WRITTEN CONSENT OF JENNIFER KEMME OR SCOTT HARRIS ARE STRICTLY PROHIBITED. 1 OF 4 PLANS PREPARED BY: JENNIFER KEMME PH: 909.748.1300 (31) SILFAB PRIME SIL-400 HC+ PEAK POWER = 400 W MAX OPERATING CURRENT = 11.10 A MAX OPERATING VOLTAGE = 36.05 V OPEN CIRCUIT VOLTAGE = 43.02 V SHORT CIRCUIT CURRENT = 11.58 A MAX SERIES FUSE RATING = 20 A TEMP. COEFF. OF Voc = -0.28%/°C DIMENSIONS = 75.3" X 40.8" X 1.4" WEIGHT = 47.4 LBS GENERAL NOTES: 1.THIS SYSTEM COMPLIES WITH THE 2022 CRC, 2022 CBC, 2022 CFC, AND THE 2022 CEC. 2.THE SYSTEM WILL NOT BE TURNED-ON UNTIL THE SERVING UTILITY COMPANY HAS BEEN NOTIFIED. 3.THE INSTALLED SOLAR SYSTEM HAS A DISTRIBUTED WEIGHT LESS THAN 4 PSF. 4.THE CONCENTRATED LOAD FOR EACH VERTICAL SUPPORT IS LESS THAN 40 LBS. 5.ALL PV EQUIPMENT IS LISTED BY A RECOGNIZED TESTING LAB. INVERTERS ARE UL 1741 COMPLIANT. 6.THE BACKFED BREAKER WILL BE LOCATED AT THE OPPOSITE END OF THE BUS FROM THE MAIN BREAKER. 7.CONDUCTORS ARE 90° C RATED COPPER WIRE. 8.ANY CONDUCTORS EXPOSED TO SUNLIGHT ARE LISTED AS SUNLIGHT RESISTANT. 9.IF DC CONDUCTORS ARE RUN INSIDE THE BUILDING, THEY WILL BE CONTAINED IN A METAL RACEWAY. 10.ANY CONDUCTORS BETWEEN SEPARATE ARRAYS ON THE ROOF WILL BE PROTECTED IN CONDUIT. 11.THE EQUIPMENT GROUNDING CONDUCTOR ON THE ROOF WILL BE PROTECTED FROM PHYSICAL DAMAGE. IT WILL BE TUCKED NEATLY UNDER THE MODULES AND RAILS AND SECURED IN PLACE. 12.THE MODULES WILL BE ATTACHED TO THE EQUIPMENT GROUNDING CONDUCTOR IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. 13.ALL EXTERIOR CONDUIT, FITTINGS AND BOXES ARE RAIN-TIGHT AND APPROVED FOR USE IN WET LOCATIONS. 14.CLEARANCES AROUND ALL ELECTRICAL EQUIPMENT WILL BE MAINTAINED IN ACCORDANCE WITH CEC 110.26. 15.SOLAR MODULES WILL NOT OBSTRUCT ANY PLUMBING, MECHANICAL OR BUILDING ROOF VENTS. 16.IF THE EXISTING MAIN SERVICE PANEL DOES NOT HAVE A VERIFIABLE GROUNDING ELECTRODE SYSTEM, A GROUNDING ELECTRODE SYSTEM WILL BE INSTALLED PER CEC 250.50. THE ELECTRICAL SERVICE WILL BE BONDED TO THE WATER AND GAS PIPING PER SECTION 250.104 OF THE CEC. 17.A LADDER WILL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH CAL-OSHA REGULATIONS. 83984PV INVERTER/DC DISCONNECT:(1) SOLAREDGE SE10000H-US MAX DC INPUT VOLTAGE = 480 V NOMINAL DC INPUT VOLTAGE = 400 V MAX DC INPUT CURRENT = 27.0 A DC DISCONNECT MAX INPUT CURRENT = 45.0 A NUMBER OF DC INPUTS = 3 RATED AC POWER = 10000 W AC VOLTAGE = 240 V MAX AC OUTPUT CURRENT = 42.0 A NEMA 4X ENCLOSURE DIMENSIONS = 21.3" X 14.6" X 7.3" WEIGHT = 39 LBS PHOTOVOLTAIC SOLAR PROJECT INFORMATION: SYSTEM SIZE:12.400 kW (DC), 10.000 kW (AC) MODULES: MODULE ADD-ON:(31) SOLAREDGE S440 DC POWER OPTIMIZERS MAX DC INPUT VOLTAGE = 60 V OPERATING VOLTAGE RANGE = 8 V - 60 V MAX DC INPUT CURRENT = 14.5 A MAX DC OUTPUT CURRENT = 15 A DC OUTPUT VOLTAGE = 380 V MAX POWER PER STRING (CONTROLLED BY INVERTER) = 5700 W NEMA 6P ENCLOSURE DIMENSIONS = 5.1" X 6.1" X 1.2" WEIGHT = 1.6 LB ARRAY:INSTALLED WEIGHT = 2.8 PSF ROOF COVERAGE = 665 SF, ARRAYS COVER 25% OF TOTAL ROOF AREA MOUNTING HARDWARE:K2 CROSSRAIL 48X RAIL K2 EVERFLASH ECOMP KIT ATTACHMENTS 5 16" STAINLESS STEEL LAG BOLTS @ 72" OC OR LESS WITH A MINIMUM OF 21 2" PENETRATION INTO ROOF RAFTERS EXISTING ROOF INFO:1 STORY, SPANISH COMPOSITION UNDER ARRAYS TILE 2 X 4 RAFTERS @ 24" OC SCOPE OF WORK: INSTALL (31) SILFAB PRIME SIL-400HC+ SOLAR ELECTRIC MODULES AND (31) SOLAREDGE S440 DC POWER OPTIMIZERS ON THE EXISTING 1ST STORY TILE ROOF. INSTALL ASSOCIATED MOUNTING HARDWARE, JUNCTION BOXES, CONDUIT, CONDUCTORS AND GROUNDING. INSTALL (1) SOLAREDGE SE10000H-US INVERTER WITH INTEGRATED DC DISCONNECT, (1) FUSED AC DISCONNECT, AND CONNECT TO SCE INSTALLED GMA. HOMEOWNER:CHRIS BERG PH: 408.510.9153 ADDRESS:74320 ASTER DRIVE PALM DESERT, CA 92260 DATE: 3/24/23 UNDERLINE ENERGY CONCEPTS INC. 18540 PASADENA STREET LAKE ELSINORE, CA 92530 PH: 951.201.1900 JESSE M. MALONE C10 - 1015714 NOTE: DIMENSIONS AND FEATURES SHOWN ARE CLOSE TO SCALE BUT WERE TAKEN FROM A FIELD SURVEY AND APPROXIMATIONS MADE USING GOOGLE EARTH. (E) 200 AMP MAIN SERVICE PANEL W/ SCE INSTALLED GMA ASTER DRIVE N SCALE: 1/16"=1' 8 16 32 48 VENT (TYP) SITE/ROOF PLAN ARRAY #2: (13) MODULES TILT = 14°, AZ = 250° 1 ARRAY #4: (6) MODULES TILT = 15°, AZ = 70° PROPERTY LINE SHEET NOTICE: ANY CHANGES TO OR USES OF THESE DOCUMENTS/DRAWINGS WITHOUT THE WRITTEN CONSENT OF JENNIFER KEMME OR SCOTT HARRIS ARE STRICTLY PROHIBITED. 2 OF 4 PLANS PREPARED BY: JENNIFER KEMME PH: 909.748.1300 NTS ELEVATION DETAIL EXISTING 1-STORY ROOF: SPANISH TILE (COMPOSITION SHINGLE UNDER ARRAYS), FELT & 1 2" SHEATHING OVER RAFTERS EXISTING 2 X 4 RAFTERS @ 24" OC 3" MIN. 8" MAX. K2 CROSSRAIL 48X RAIL MOUNTING SYSTEM WITH K2 EVERFLASH ECOMP KIT ROOF ATTACHMENTS (USE 5 16" STAINLESS STEEL LAG BOLTS @ 72" OC OR LESS WITH A MINIMUM EMBEDMENT OF 21 2" INTO ROOF RAFTERS), WATERPROOF ALL CONNECTION LOCATIONS PER MANUFACTURER'S INSTRUCTIONS MODULES: 75.3" X 40.8" 47.4 LBS EACH 1.5' FIRE CLEARANCE 83984PV ROOF ACCESS POINTS ARE AT THE STRUCTURALLY STRONG PART OF THE BUILDING AND DO NOT REQUIRE LADDERING OVER OPENINGS. * TOTAL ROOF AREA = 2625 SF TOTAL SOLAR AREA = 665 SF 665 SF/2625 SF = 0.25 ARRAYS COVER 25% OF TOTAL ROOF AREA 27'-9" 5'-4" 16' 13'-5" ARRAY #1: (4) MODULES TILT = 14°, AZ = 250° ARRAY #3: (8) MODULES TILT = 19°, AZ = 340°2 3 4 17 16 15 5 6 7 8 9 10 11 12 13 14 18192021 22232425 26 27 28 29 30 31 2'-3"1'-3" 1'-6" 5'-7" 3' 3' 4' * * (N) FUSED AC DISCONNECT (N) INVERTER/ DC DISCONNECT PROPERTY LINE PROPERTY LINE SCOPE OF WORK: INSTALL (31) SILFAB PRIME SIL-400HC+ SOLAR ELECTRIC MODULES AND (31) SOLAREDGE S440 DC POWER OPTIMIZERS ON THE EXISTING 1ST STORY TILE ROOF. INSTALL ASSOCIATED MOUNTING HARDWARE, JUNCTION BOXES, CONDUIT, CONDUCTORS AND GROUNDING. INSTALL (1) SOLAREDGE SE10000H-US INVERTER WITH INTEGRATED DC DISCONNECT, (1) FUSED AC DISCONNECT, AND CONNECT TO SCE INSTALLED GMA. HOMEOWNER:CHRIS BERG PH: 408.510.9153 ADDRESS:74320 ASTER DRIVE PALM DESERT, CA 92260 DATE: 3/24/23 UNDERLINE ENERGY CONCEPTS INC. 18540 PASADENA STREET LAKE ELSINORE, CA 92530 PH: 951.201.1900 JESSE M. MALONE C10 - 1015714 ELECTRICAL LINE DIAGRAM SHEET NOTICE: ANY CHANGES TO OR USES OF THESE DOCUMENTS/DRAWINGS WITHOUT THE WRITTEN CONSENT OF JENNIFER KEMME OR SCOTT HARRIS ARE STRICTLY PROHIBITED. 3 OF 4 PLANS PREPARED BY: JENNIFER KEMME PH: 909.748.1300 (3) 6 AWG THHN-2/THWN2 & (1) 8 AWG GROUND IN 3 4" EMT CONDUIT L1 L2 N G SOLAREDGE INTEGRATED DC DISCONNECT & RAPID SHUTDOWN DEVICE SOLAREDGE SE10000H-US 240 VAC, 1Ø TRANSFORMERLESS INVERTER - + CONDUIT MUST BE SUPPORTED A MINIMUM OF 7 8" ABOVE THE ROOF SURFACE. 83984PV + - + - SOURCE CIRCUIT #1: 10 MODULES, 600 VDC + - + - (6) 10 AWG PV IN AIR (10) 600 VDC SOLAREDGE S440 OPTIMIZERS + - + - SOURCE CIRCUIT #2: 10 MODULES, 600 VDC + - + - (10) 600 VDC SOLAREDGE S440 OPTIMIZERS NEMA 3R, 600 VDC JUNCTION BOX (6) 10 AWG THHN-2/THWN & (1) 8 AWG GROUND IN 3 4" EMT CONDUIT + - + - SOURCE CIRCUIT #3: 11 MODULES, 600 VDC + - + - (11) 600 VDC SOLAREDGE S440 OPTIMIZERS USE K2 INTEGRATED GROUNDING TO GROUND ALL MODULES, OPTIMIZERS, JUNCTION BOXES AND ANY OTHER METAL PARTS AND #6 AWG SOLID COPPER WHERE NECESSARY SILFAB PRIME SIL-400HC+ SILFAB PRIME SIL-400HC+ SILFAB PRIME SIL-400HC+ SILFAB PRIME SIL-400HC+ SILFAB PRIME SIL-400HC+ SILFAB PRIME SIL-400HC+ MAIN SERVICE INFO: 200 A, 120/240 VAC, 1Ø, 3-WIRE METER #222013-539596 200A EXISTING BUILDING GROUNDING ELECTRODE SYSTEM M EXISTING SERVICE PANEL W/SCE INSTALLED GMA: 200 A BUS RATED, 240 VAC, 1Ø 60A G L1 L2 60 A, 240 VAC, 1Ø FUSED AC DISCONNECT LOCKABLE, VISIBLE KNIFE-BLADE TYPE (3) 6 AWG THHN-2/THWN2 IN 3 4" LFNC CONDUIT SCOPE OF WORK: INSTALL (31) SILFAB PRIME SIL-400HC+ SOLAR ELECTRIC MODULES AND (31) SOLAREDGE S440 DC POWER OPTIMIZERS ON THE EXISTING 1ST STORY TILE ROOF. INSTALL ASSOCIATED MOUNTING HARDWARE, JUNCTION BOXES, CONDUIT, CONDUCTORS AND GROUNDING. INSTALL (1) SOLAREDGE SE10000H-US INVERTER WITH INTEGRATED DC DISCONNECT, (1) FUSED AC DISCONNECT, AND CONNECT TO SCE INSTALLED GMA. HOMEOWNER:CHRIS BERG PH: 408.510.9153 ADDRESS:74320 ASTER DRIVE PALM DESERT, CA 92260 DATE: 3/24/23 UNDERLINE ENERGY CONCEPTS INC. 18540 PASADENA STREET LAKE ELSINORE, CA 92530 PH: 951.201.1900 JESSE M. MALONE C10 - 1015714 SYSTEM SIGNAGESYSTEM SIGNAGE ALL SIGNAGE SHALL BE REFLECTIVE, UV RESISTANT PLASTIC, RED IN COLOR WITH WHITE LETTERING, AND ATTACHED WITH WEATHERPROOF ADHESIVE OR OTHER APPROVED METHOD. ALL LETTERS SHALL BE A MINIMUM OF 3 8" HEIGHT AND ALL CAPITALIZED. ALL CONDUIT, JUNCTION BOXES AND OTHER ENCLOSURES SHALL BE MARKED AT 10' MAX INTERVALS AND AT ALL BENDS, TERMINATIONS, SPLICES OR CONNECTIONS WITH "WARNING: PHOTOVOLTAIC POWER SOURCE". WARNING ELECTRIC SHOCK HAZARD DO NOT TOUCH TERMINALS TERMINALS ON BOTH THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION TO BE INSTALLED AT ALL SERVICEABLE PANELS OR BOXES AND AT ALL DISCONNECTS: WARNING ELECTRIC SHOCK HAZARD THE DC CONDUCTORS OF THIS PHOTOVOLTAIC SYSTEM ARE UNGROUNDED MAY BE ENERGIZED SERVICE POINT & UTILITY METERING CAUTION: POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS AS SHOWN. ADDRESS: 74320 ASTER DRIVE, PALM DESERT, CA 92260 SOLAR ARRAY (ON ROOF) N INVERTER & DC DISCONNECT TO BE INSTALLED ON THE OUTSIDE COVER OF THE MAIN SERVICE DISCONNECT: PV SOLAR DC DISCONNECT MAXIMUM VOLTAGE = 480.00 V MAXIMUM CIRCUIT CURRENT = 45.00 A MAXIMUM RATED OUTPUT CURRENT OF THE DC-TO-DC CONVERTER = 15.00 A TO BE INSTALLED ON THE FRONT OF THE DC DISCONNECT: RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM RATED AC OUTPUT CURRENT = 52.25 A NOMINAL OPERATING AC VOLTAGE = 240 V TO BE INSTALLED ON THE FRONT OF THE AC DISCONNECT: WARNING POWER SOURCE OUTPUT CONNECTION - DO NOT RELOCATE THIS OVERCURRENT DEVICE TO BE INSTALLED AT THE BACKFED BREAKER SERVING THE PV SOLAR SYSTEM: TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN THE ARRAY SOLAR ELECTRIC PV PANELS SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN TO BE INSTALLED ON THE FRONT OF THE MAIN SERVICE DISCONNECT: "SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN" SHALL BE BLACK LETTERING ON YELLOW BACKGROUND. THE REMAINDER OF THE SIGN SHALL BE BLACK LETTERING ON WHITE BACKGROUND. SHEET NOTICE: ANY CHANGES TO OR USES OF THESE DOCUMENTS/DRAWINGS WITHOUT THE WRITTEN CONSENT OF JENNIFER KEMME OR SCOTT HARRIS ARE STRICTLY PROHIBITED. 4 OF 4 PLANS PREPARED BY: JENNIFER KEMME PH: 909.748.1300 SYSTEM CALCULATIONS: MODULE POWER = 400 W NUMBER OF MODULES IN LONGEST STRING = 11 (11) 400 W = 4400 W OPTIMIZER MAX POWER PER STRING = 6000 W 4400 W < 6000 W, OK OPERATING CURRENT = POWER RATING/OPERATING VOLTAGE = 4400 W/400 V = 11.00 A OPTIMIZER TO INVERTER TARGET VOLTAGE/OPERATING VOLTAGE = 400 V MAX SYSTEM VOLTAGE (Voc) CONTROLLED BY INVERTER = 480 V SHORT-CIRCUIT CURRENT (Isc) CONTROLLED BY OPTIMIZER = 15.00 A INVERTER MAX OUTPUT CURRENT = 42.00 A 42.00 A (1.25) = 52.50 A [Ic], USE 60 A FUSE WIRE CALCULATIONS: FROM OPTIMIZERS TO INVERTER/DC DISCONNECT: AMBIENT TEMPERATURE = 47°C TEMPERATURE ADDER FOR CONDUIT OFFSET FROM ROOF BY MIN 7 8"= 0°C ADJUSTMENT FACTOR PER TABLE 310.15(B)(2)(a) FOR 90°C INSULATED CONDUCTOR AT 47°C + 0°C = 69°C = 0.82 Isc = 15.00 A 15.00 A/0.82 = 18.29 A NUMBER OF CURRENT CARRYING CONDUCTORS IN CONDUIT = 6 ADJUSTMENT FACTOR PER TABLE 310.15(B)(3)(a) FOR CONDUIT FILL (4-6 CONDUCTORS IN CONDUIT) = 0.80 18.29 A/0.80 = 22.31 A SELECT WIRE SIZE WITH AMPACITY GREATER THAN 22.31 A, USE 10 AWG THWN-2 COPPER WIRE WITH AN AMPACITY OF 40 A SELECT CONDUIT FOR (4) 10 AWG THHN-2/THWN & (1) 8 AWG GROUND = 3 4" EMT CONDUIT FROM THE INVERTER TO THE MAIN SERVICE PANEL: ADJUSTMENT FACTOR PER TABLE 310.15(B)(2)(a) FOR 90°C INSULATED CONDUCTOR AT 47°C = 0.87 Ic = 52.25 A 52.25 A/0.91 = 60.01 A SELECT WIRE SIZE WITH AMPACITY GREATER THAN 60.01 A, USE 6 AWG THHN-2/THWN COPPER WIRE WITH AN AMPACITY OF 75 A SELECT CONDUIT FOR (3) 6 AWG THHN-2/THWN & (1) 8 AWG GROUND = 3 4" EMT CONDUIT 83984PV PV SYSTEM DISCONNECT FOR UTILITY OPERATION SIL-400 HC+ SI L FABS OL AR . CO M R ELI A BLE E NE RG Y. DI RECT F R OM T HE S O UR CE. Designed to outperform. Dependable, durable, high-performance solar panels engineered for North American homeowners. SILFAB SOLAR INC. 800 Cornwall Ave Bellingham WA 98225 USA T +1 360.569.4733 info@silfabsolar.com SI L FABS OL AR .COM 1770 Port Drive Burlington WA 98233 USA T +1 360.569.4733 240 Courtneypark Drive East Mississauga ON L5T 2Y3 Canada T +1 905.255.2501 F +1 905.696.0267 Silfab - SIL-400-HC+-20221228 No reproduction of any kind is allowed without permission. Data and information is subject to modifications without notice. © Silfab Solar Inc., 2022. Silfab Solar® is a registered trademark of Silfab Solar Inc. ELECTRICAL SPECIFICATIONS 400 Test Conditions STC NOCT Module Power (Pmax) Wp 400 298 Maximum power voltage (Vpmax) V 36.05 33.50 Maximum power current (Ipmax) A 11.10 8.90 Open circuit voltage (Voc) V 43.02 40.35 Short circuit current (Isc) A 11.58 9.34 Module eTiciency % 20.2% 18.8% Maximum system voltage (VDC)V 1000 Series fuse rating A 20 Power Tolerance Wp 0 to +10 Measurement conditions: STC 1000 W/mS • AM 1.5 • Temperature 25 °C • NOCT 800 W/mS • AM 1.5 • Measurement uncertainty ≤ 3% Sun simulator calibration reference modules from Fraunhofer Institute. Electrical characteristics may vary by ±5% and power by 0 to +10W. TEMPERATURE RATINGS Temperature CoeTicient Isc +0.064 %/°C Temperature CoeTicient Voc -0.28 %/°C Temperature CoeTicient Pmax -0.36 %/°C NOCT (± 2°C) 45 °C Operating temperature -40/+85 °C WARRANTIES Module product workmanship warranty 25 years** Linear power performance guarantee 30 years ≥ 97.1% end 1st yr ≥ 91.6% end 12th yr ≥ 85.1% end 25th yr ≥ 82.6% end 30th yr SHIPPING SPECS Modules Per Pallet: 26 or 26 (California) Pallets Per Truck 32 or 31 (California) Modules Per Truck 832 or 806 (California) CERTIFICATIONS Product UL 61215-1:2017 Ed.1, UL 61215-2:2017 Ed.1, UL 61730-1:2017 Ed.1, UL 61730- 2:2017 Ed.1, CSA C22.2#61730-1:2019 Ed.2, CSA C22.2#61730-2:2019 Ed.2, IEC 61215-1:2016 Ed.1, IEC 61215-2:2016 Ed.1, IEC 61730-1:2016 Ed.2, IEC 61730-2:2016 Ed.2, IEC 61701:2020 (Salt Mist Corrosion), IEC 62716:2013 (Ammonia Corrosion), UL Fire Rating: Type 2, CEC Listing*** Factory ISO9001:2015 MECHANICAL PROPERTIES / COMPONENTS METRIC IMPERIAL Module weight 21.3kg ±0.2kg 47lbs ±0.4lbs Dimensions (H x L x D) 1914 mm x 1036 mm x 35 mm 75.3 in x 40.8 in x 1.37 in Maximum surface load (wind/snow)* 5400 Pa rear load / 5400 Pa front load 112.8 lb/P2 rear load / 112.8 lb/P2 front load Hail impact resistance ø 25 mm at 83 km/h ø 1 in at 51.6 mph Cells 132 Half cells - Si mono PERC 9 busbar - 83 x 166 mm 132 Half cells- Si mono PERC 9 busbar - 3.26 x 6.53 in Glass 3.2 mm high transmittance, tempered, DSM antireflective coating 0.126 in high transmittance, tempered, DSM antireflective coating Cables and connectors (refer to installation manual) 1350 mm, ø 5.7 mm, MC4 from Staubli 53 in, ø 0.22 in (12AWG), MC4 from Staubli Backsheet High durability, superior hydrolysis and UV resistance, multi-layer dielectric film, fluorine-free PV backsheet Frame Anodized Aluminum (Black) Bypass diodes 3 diodes-30SQ045T (45V max DC blocking voltage, 30A max forward rectified current) Junction Box UL 3730 Certified, IEC 62790 Certified, IP68 rated * Warning. Read the Safety and Installation Manual for mounting specifications and before handling, installing and operating modules. ** 12 year extendable to 25 years subject to registration and conditions outlined under “Warranty” at silfabsolar.com. PAN files generated from 3rd party performance data are available for download at: silfabsolar.com/downloads. *** CEC listing in progress. January 2023, expected completion. Si d e Ba c k V i e w Pr o f i l e 75.3" [1914mm] 1. 4 " [ 3 5 m m ] 1.4" [35mm] 1. 4 " [ 3 5 m m ] 0.06" [1.5mm] 0.5" [12mm] 0. 3 " [ 7 m m ] 0. 6 " [ 1 5 m m ] 40 . 8 " [ 1 0 3 6 m m ] 12.1" [307mm]51.2 [1300mm] 12.1" [307mm] Ø0 . 1 7 " [ Ø 4 . 2 m m ] ( x 2 ) Gr o u n d i n g H o l e Mounting Hole (x4) Drainage Hole (x8) 39 . 2 " [ 9 9 6 m m ] 2.4" [60mm]8" [200mm] 53.15" [1350mm] Cable Length VRODUHGJHFRP 2SWLPL]HGLQVWDOODWLRQZLWK+':DYHWHFKQRORJ\ SpeciÀcallydesignedtoworkwithpoweroptimizers Built-inmodule-levelmonitoring Optional:Fasterinstallationswithbuilt-inconsumption metering(1%accuracy)andproductionrevenuegrade metering(0.5%accuracy,ANSIC12.20) Record-breaking99%weightede඼ciency Quickandeasyinvertercommissioningdirectly fromasmartphoneusingtheSolarEdgeSetApp Fixedvoltageinverterforlongerstrings UL1741SAcertiÀed,forCPUCRule21gridcompliance Integratedarcfaultprotectionandrapid shutdownforNEC2014and2017,perarticle 690.11and690.12 Small,lightweight,andeasytoinstallbothoutdoors orindoors 6LQJOH3KDVH,QYHUWHUZLWK+':DYH7HFKQRORJ\ IRU1RUWK$PHULFD SE3000H-US/SE3800H-US/SE5000H-US/SE6000H-US/ SE7600H-US/SE10000H-US/SE11400H-US  <($5:$55$17< 02 '(/180%(5 6(+86 6(+86 6(+86 6(+86 6(+86 6(+86 6(+86 $33/,&$%/(72,19(57(56:,7+3$57180%(5 6(;;;;+;;;;;%;; 287387 5DWHG$&3RZHU2XWSXW  #9#9 #9#9   #9#9 9$ 0D[LPXP$&3RZHU2XWSXW  #9#9 #9#9   #9#9 9$ $&2XWSXW9ROWDJH0LQ1RP0D[        9DF $&2XWSXW9ROWDJH0LQ1RP0D[   9DF $&)UHTXHQF\ 1RPLQDO   +] 0D[LPXP&RQWLQXRXV2XWSXW&XUUHQW#9        $ 0D[LPXP&RQWLQXRXV2XWSXW&XUUHQW#9        3RZHU)DFWRU 1,Adjuᐎable-0.85to0.85 *)',7KUHVKROG  $ 8WLOLW\0RQLWRULQJ,VODQGLQJ3URWHFWLRQCountryConÀgurableThresholds <HV ,1387 0D[LPXP'&3RZHU#9        : 0D[LPXP'&3RZHU#9        7UDQVIRUPHUOHVV8QJURXQGHG<HV 0D[LPXP,QSXW9ROWDJH 9GF 1RPLQDO'&,QSXW9ROWDJH  9GF 0D[LPXP,QSXW&XUUHQW#9         $GF 0D[LPXP,QSXW&XUUHQW#9         $GF 0D[,QSXW6KRUW&LUFXLW&XUUHQW  $GF 5HYHUVH3RODULW\3URWHFWLRQ <HV *URXQG)DXOW,VRODWLRQ'HWHFWLRQ N 6HQVLWLYLW\ MaximumInverterE੕ciency   CECWeightedE੕ciency #9#9  1LJKWWLPH3RZHU&RQVXPSWLRQ  :  )RURWKHUUHJLRQDOVHWWLQJVSOHDVHFRQWDFW6RODU(GJHVXSSRUW  Ahighercurrentsourcemaybeused;theinverterwilllimititsinputcurrenttothevaluesᐎated 6LQJ OH3KDVH,QYHUWHU ZLWK+':DYH7HFKQRORJ\IRU1RUWK$PHULFD SE3000H-US/SE3800H-US/SE5000H-US/SE6000H-US/ SE7600H-US/SE10000H-US/SE11400H-US 02 '(/180%(5 6(+86 6(+86 6(+86 6(+86 6(+86 6(+86 6(+86 $'',7,21$/)($785 (6 6XSSRUWHG&RPPXQLFDWLRQ,QWHUIDFHV 56(WKHUQHW=LJ%HH RSWLRQDO &HOOXODU RSWLRQDO 5HYHQXH*UDGH0HWHULQJ$16,&2SWLRQDO  &RQVXPSWLRQPHWHULQJ ,QYHUWHU&RPPLVVLRQLQJ WiththeSetAppmobileapplicationusingBuilt-inWi-FiAccessPointforLocalConnection 5DSLG6KXWGRZQ1(&DQG$XWRPDWLF5DSLG6KXWGRZQXSRQ$&*ULG'LVFRQQHFW 67$1'$5 '&203 /,$1 &( 6DIHW\UL1741,UL1741SA,UL1699B,CSAC22.2,CanadianAFCIaccordingtoT.I.L.M-07 *ULG&RQQHFWLRQ6WDQGDUGV ,(((5XOH5XOH +, (PLVVLRQV )&&3DUW&ODVV% ,167$//$7 ,2163 (&,),&$7 ,216 $&2XWSXW&RQGXLW6L]H$:*5DQJH  0D[LPXP$:*  0D[LPXP$:* '&,QSXW&RQGXLW6L]HRI6WULQJV$:*5DQJH 1''Maximum/1-2ᐎrings/14-6AWG 1''Maximum/1-3ᐎrings/14-6AWG 'LPHQVLRQVZLWK6DIHW\6ZLWFK +[:[' [[[[ [[[[ LQPP :HLJKWZLWK6DIHW\6ZLWFK    lb/kg 1RLVH  G%$ &RROLQJ 1DWXUDO&RQYHFWLRQ 2SHUDWLQJ7HPSHUDWXUH5DQJH WRWR  ˚F/˚C 3URWHFWLRQ5DWLQJ1(0$; ,QYHUWHUZLWK6DIHW\6ZLWFK  InverterwithRevenueGradeMeterP/N:SExxxxH-US000BNC4;InverterwithRevenueGradeProductionandConsumptionMeterP/N:SExxxxH-US000BNI4.Forconsumptionmetering,currenttransformersshouldbeorderedseparately:SEACT0750-200NA-20orSEACT0750-400NA-20.20unitsperbox  Fullpoweruptoatleaᐎ50˚C/122˚F;forpowerde-ratinginformationreferto:https://www.solaredge.com/sites/default/Àles/se-temperature-derating-note-na.pdf 6LQJOH3KDVH,QYHUWHU ZLWK+':DYH7HFKQRORJ\IRU1RUWK$PHULFD SE3000H-US/SE3800H-US/SE5000H-US/SE6000H-US/ SE7600H-US/SE10000H-US/SE11400H-US ©SolarEdgeTechnologies,Inc.Allrightsreserved.SOLAREDGE,theSolarEdgelogo,OPTIMIZEDBYSOLAREDGEaretrademarksorregisteredtrademarksofSolarEdgeTechnologies,Inc.All othertrademarksmentionedhereinaretrademarksoftheirrespectiveowners.Date:01/2020/V01/ENGNAM.Subjecttochangewithoutnotice. +RZWR(QDEOH&RQVXPSWLRQ0RQLWRULQJ Bysimplywiringcurrenttransformersthroughtheinverter'sexistingACconduitsandconnectingthemtotheservicepanel,homeownerswillgainfullinsightintotheir householdenergyusagehelpingthemtoavoidhighelectricitybills