HomeMy WebLinkAboutRes 04-127 Energy Efficiency Loan from California Energy CommissionCITY OF PALM DESERT COMMUNITY SERVICES STAFF REPORT REQUEST: APPROVAL OF APPLICATION FOR AN ENERGY EFFICIENCY LOAN FROM THE CALIFORNIA ENERGY COMMISSION TO IMPLEMENT ENERGY EFFICIENCY MEAURES SUBMITTED BY: Robert Kohn, Director of Special Programs DATE: December 9, 2004 CONTENTS: 1. Resolution 2. Energy Efficiency Study Final Report Recommendation 1. Waive Further Reading and Adopt Resolution No. 04-127 2. Authorize the Mayor to sign the California Energy Commission Loan Application and Loan Agreement in the amount of $197,135. Executive Summary The City Council adopted Resolution No. 04-35 at the May 13, 2004 meeting authorizing the application for the California Energy Commission's Assistance Program. The program provides technical assistance and low interest loans for the implementation of projects to reduce energy costs in local government facilities. The Palm Desert study is based on a site survey performed in August 2004; a review of historical utility data; information provided by City personnel; and engineering analysis work. The objective of the study was to identify feasible energy saving projects at the City Hall facility. The study has been completed and several projects have been identified for loan funding by the California Energy Commission (CEC). Staff Report December 9, 2004 Energy Efficiency Loan Discussion Resolution No. 04-127 The criteria for selected projects are that they must have a simple payback period of 10 years with debt service covered by the energy savings. The projects identified in the analysis meet the criteria and include a 50 kW photovoltaic system, lighting retrofit, and some additional HVAC Controls. The total project cost is $331,753 with rebates and other incentives of $132,854. The proposed loan application is for $197,135. The annual savings will be $19,210/yr. resulting in no additional costs to the City in making the loan payments. The Self Generation incentives and California Energy Commission Loan must be applied for or reserved prior to January 1, 2005 in order to secure the funds and loan interest rate of 3.95%. Staff has reserved the incentives through Southern California Edison for the 50 kW photovoltaic system. Mr. Leonard Wolk of REASCO has reviewed the CEC analysis and concurs with the findings. Submitted by: 4��X� ROBERT KOHN, Director Special Programs Approval: City Manager Finance . it ctor + ler A RESOLUTION OF THE CITY COUNCIL OF THE CITY OF PALM DESERT AUTHORIZING THE APPLICATION FOR AN ENERGY EFFICIENCY LOAN FROM THE CALIFORNIA ENERGY COMMISSION TO IMPLEMENT ENERGY EFFICIENCY MEASURES RESOLUTION NO. 04-127 WHEREAS, the California Energy Commission provides loans to schools, hospitals, local governments, special districts, and public care institutions to finance energy efficiency improvements; NOW, THEREFORE, BE IT RESOLVED by the City Council authorizes the City of Palm Desert to apply for an energy efficiency loan from the California Energy Commission to implement energy efficiency measures. BE IT ALSO RESOLVED, that the amount of the loan will be paid in full, plus interest, under the terms and conditions of the loan agreement of the California Energy Commission. BE IT FURTHER RESOLVED, that the Mayor is hereby authorized and empowered to execute in the name of the City of Palm Desert all necessary documents to implement and carry out the purpose of this resolution, and to undertake all actions necessary to undertake and complete projects. PASSED, APPROVED AND ADOPTED by the City Council of the City of Palm Desert at the regular meeting held this 9t" day of December, 2004 by the following vote: AYES: Councilmember: NOES: Councilmember: ABSENT: Councilmember: ABSTAIN: Councilmember: ROBERTS. SPIEGEL, MAYOR ATTEST: RACHELLE KLASSEN, CITY CLERK (�7 RESOLUTION NO. 04-35 A RESOLUTION OF THE CITY COUNCIL OF THE CITY OF PALM DESERT APPROVING THE "REQUEST FOR ASSISTANCE" FROM THE CALIFORNIA ENERGY COMMISSION FOR DEVELOPMENT OF AN ENERGY EFFICIENCY, COGENERATION PROJECT AT CITY HALL WHEREAS, the California Energy Commission has developed the Energy Partnership Program to provide technical assistance in identifying energy efficiency improvements; WHEREAS, the City Council of the City of Palm Desert authorizes the City Manager, to apply for technical assistance from the California Energy Commission; . WHEREAS, the City Council of the City of Palm Desert recognizes that the California Energy Commission has limited funds for technical assistance and that primary consideration will be given to those that are committed to implementing the recommended projects identified through the Energy Partnership Program; WHEREAS, the City of Palm Desert intends to apply for assistance from the California ,Energy Commission for development of an Energy Efficiency and Cogeneration Project at City Hall; WHEREAS, the City of Palm Desert will enter into agreements with the California Energy Commission; NOW, THEREFORE, BE IT RESOLVED, that the City Council of the City of Palm Desert, California, authorizes the following: 1. The submittal of an application to the California Energy Commission's Energy Partnership Program. 2. The City Manager, or a designee, is hereby authorized and empowered to execute in the name of the City of Palm Desert all necessary applications, forms, contracts, payment requests, agreements, and amendments hereto for the purpose of obtaining technical assistance and funding for energy efficiency improvements to City Hall. ENERGY EFFICIENCY STUDY For CITY HALL CITY OF PALM DESERT PALM DESERT, CALIFORNIA FINAL REPORT CALIFORNIA ENERGY COMMISSION ENERGY PARTNERSHIP PROGRAM Contract No. 400-00-079 Work Authorization No. 43 Prepared by SERVIDYNE SYSTEMS, LLC 1945 The Exchange, Suite 325 Atlanta, GA 30339 (800) 241-8996 December 2004 TABLE OF CONTENTS EXECUTIVESUMMARY..............................................................................................................I INTRODUCTION AND FACILITY BACKGROUND..................................................................3 CURRENTENERGY OVERVIEW...............................................................................................4 EnergyUse Profile...............................................................................................................4 LightingSystems..................................................................................................................8 HVACSystems....................................................................................................................9 Miscellaneous Energy Systems..........................................................................................11 RECOMMENDED ENERGY PROJECTS...................................................................................12 LightingProjects................................................................................................................12 HVACProjects..:...............................................................................................................16 SolarProjects.....................................................................................................................17 ADDITIONALISSUES.................................................................................................................19 APPENDIX A: HISTORICAL ENERGY USE......................................................................... A-1 APPENDIX B: ENGINEERING CALCULATIONS.................................................................B-1 APPENDIX C: MANUFACTURERS' PRODUCT LITERATURE..........................................C-1 EXECUTIVE SUMMARY The City of Palm Desert spent $85,402 for electricity and natural gas use at City Hall during the 12- month period between October 2003 and September 2004. Annual energy expenditures can be reduced by approximately $19,200, or 22% of utility bills, if the energy projects recommended in this report are implemented. The net cost to implement these measures, after anticipated incentive rebates, is just over $197,000, resulting in an average payback of 10.3 years. The table on the following page summarizes the recommended measures, their annual energy savings, installation costs, and simple payback periods. The City Hall facility is currently operating fairly efficiently. The City has implemented a number of significant energy measures over the past several years. These include installation of a solar PV system, a cool roof retrofit, replacement of older rooftop HVAC units with high efficiency models, installation of programmable thermostats, replacement of incandescent interior lighting with compact fluorescent, conversion of mercury vapor exterior eave lighting to compact fluorescent, and installation of LED exit sign retrofits. The building envelope is well insulated, and the glazing is inset with deep overhangs for solar shading. In addition, the building expansion in 1990 incorporated skylights and a daylight dimming system for interior fluorescent lighting, as well as occupancy sensor lighting controls. Several of the recommendations in this report expand on measures already implemented by the City. The most significant project involves installation of a larger solar PV system with a capacity rating of 50 kWDC. The size selection of this system was based on available electrical infrastructure on site as well as overall payback considerations. The financial viability of this project depends on the availability of incentive rebate funding. The economic analysis in this report assumes that Self Generation Incentive Program funds will be available from Southern California Edison at the time of project implementation, at a reduced rate from the previous $4.50 per watt to the anticipated $3.00 per watt for the 2005 program. Three lighting projects are also recommended: replacement of remaining incandescent exterior lighting with compact fluorescent, conversion of all T-12 interior fluorescent lighting to T-8 lamps with electronic. ballasts, and replacement of remaining fluorescent exit signs with LED exit signs. The T-8 lighting project analysis assumes that an SCE rebate will be available at the same rates that were applicable in the 2004 Express Efficiency rebate program. One HVAC measure included in the report calls for re -programming the thermostat schedules and temperature settings for several of the rooftop units. While most of the programmable thermostats in the facility were observed to be set up correctly, approximately 15 percent had incorrect time and/or temperature settings that were causing excess energy use. This report begins with an overview of the current energy use and energy -using systems at City Hall. The report then describes the recommended energy saving projects. Each project description includes a discussion of the implementation work scope and a summary of the economic analysis. Additional issues that could not be addressed as recommended projects but may warrant further action are discussed at the end of the report. Appendices provide historical energy usage and cost data, detailed engineering calculations, and sample product literature. 1 RECOMMENDED ENERGY PROJECTS Peak Annual Annual Annual Project Simple Project Demand Elec Nat Gas Cost Cost Payback Description Savings Savings Savings Savings Estimate (years) (kW) (kWh) (Therms) Lighting Projects 1. Compact Fluorescent 0.0 5,256 0 $451 $202 0.4 Exterior Lamps 2. T-8 Lamps and 20.9 58,514 0 $8,325 $33,715' 4.0 Electronic Ballasts 3. LED Exit Signs 0.1 1,191 0 $123 $717 5.8 HVAC Projects 1. Thermostat 0.0 20,537 0 $1,764 --- Immediate Programming Solar Projects 1. Solar PV System 31.9 63,718 0 $8,547 $162,500' 19.0 Total 52.9 I 149,216 0 I $19,210 I $197,135 10.3 Notes: 1. Cost shown is net amount after applying SCE rebate of $5,354, based on 2004 program rates. 2. Cost shown in net amount after applying Self Generation Incentive Program funding of $127,500, based on 2005 anticipated program rate of $3.00 per AC watt. 2 INTRODUCTION AND FACILITY BACKGROUND This report is the result of an energy efficiency study performed under the Energy Partnership Program of the California Energy Commission. The program provides technical assistance and low interest loans for the implementation of projects to reduce energy costs in local government facilities. This study is based on a site survey performed in August 2004; a review of historical utility data; information provided by City personnel; and engineering analysis work. We appreciate the valuable assistance and support provided by Robert Kohn and David Flint of the City of.Palm Desert, during the course of the study. The objective of this study was to identify feasible energy saving projects at the City Hall facility. The original building was constructed in 1983 and consisted of three sections: the, Council Chambers, the Administrative Services wing, and the Environmental Services wing. The facility was expanded in 1990 with the addition of the North wing and East wing. The building areas are summarized in the table below. Building Area I Square Feet I Year Constructed Council Chambers 6,127 1983 Admin Svcs 8,427 1983 Environ Svcs 10,274 1983 North Wing 9,920 1990 East Wing 10,485 1990 Total 1 45,233 In addition to the City Council meeting facility, the building houses offices for the City Manager, the Mayor and various City service departments. The floor plans include open and private office areas, conference rooms and break rooms. There are also two lobby areas with wall exhibits on display. The masonry building is well -insulated with R-30 roof insulation. Glazing is double pane tinted insulating glass, inset with deep overhang shading. The North and East wings have skylights. The offices are generally occupied from 8 AM to 5 PM, Monday through Friday, year-round. Janitors clean the building during a six -hour period in the evenings. The Council Chambers are used only intermittently - for City Council meetings, which are held every other Thursday, except in August. The Council Chambers are also used for community meetings and hearings, which are generally scheduled one to four nights per week. 3 CURRENT ENERGY OVERVIEW Ener--v Use Profile The City of Palm Desert spent $85,402 for energy consumed by City Hall in the 12-month period between October 2003 and September 2004. Electricity accounted for 99 percent of the cost; natural gas totaled only 1 percent. The annual energy use for City Hall is summarized below: Electricity Natural Gas Total Cost Facility Usage I Cost Usage Cost ($) (kWh) I M (Therms) M City Hall I 613,525 j $84,502 1 822 I $900 I $85,402 Southern California Edison (SCE) supplies electricity through one meter serving City Hall. Service is provided under SCE Rate GS-2 TOU. The current rates, which came into effect in August 2004, are approximately 4 percent lower than those reflected in the historical data presented above. GS-2 TOU has both demand and time -of -use energy cost components. These components are summarized in the table below. The On -Peak period runs from Noon to 6 PM on summer weekdays except holidays. Summer Mid -Peak runs from 8 AM to Noon and 6 PM to 11 PM on non -holiday weekdays. Winter Mid -Peak runs from 8 AM to 9 PM non -holiday weekdays. Off - Peak hours are all the remaining night, weekend and holiday time periods. Rate GS-2 TOU Component Summer Winter (Jun —Sep) (Oct -May) t Demand $15.12 $6.21 (per kW per Month) On -Peak Energy $0.1298 --- (per kWh) Mid -Peak Energy $0.0934 $0.0986 (per kWh) Off -Peak Energy $0.0830 $0.0830 (per kWh) Note: kWh rates include all applicable surcharges and are based on the recent historical average of 28 percent DWR supplied electricity. There are several alternative GS-2 rates available from SCE on an optional basis. These include TOU-GS-2A and TOU-GS-2H. We analyzed these rates for the City Hall load profile and determined that the current GS-2 TOU rate is the most favorable. The City is not eligible for the non -time -of -use GS-2 rate, because the facility's maximum demand exceeds 200 kW. If implementation of energy projects reduces the maximum demand to below 200 kW, after 12 n months the City would be able to switch to rate GS-2, which would reduce the annual electric rate by approximately 3 percent. Southern California Gas supplies the City with natural gas service under Rate GN-10. This rate includes a customer charge, a fixed transmission charge and a monthly fluctuating procurement charge. The total cost per therm over the past year has averaged $1.09. The graphs below illustrate the monthly electric usage and demand, as well as natural gas usage for the building. The electricity graphs show an expected high electric usage and demand in the summer months when air conditioning loads are greatest. The natural gas graph shows highest usage in winter months due to heating load. 70,000 50,000 50,000 L 40,000 Y 30,000 20,000 10,000 0 300 250 200 Y Y 150 m a� d 100 E 50 0� City Hall BASELINE ELECTRICAL ENERGY USAGE ■ 2003 p 2004 City Hall BASELINE ELECTRICAL DEMAND ■ 2003 a 2004 5 Aug Sep Ocf Nov Dec City Hall BASELINE NATURAL GAS USAGE 350 - 300 250 M 200 E L d H 150 100 50 0 City Hall has a total annual energy cost of $1.89 per square foot, which is very reasonable for a facility of this type. The total energy use is 48,100 Btu/sq.ft./year, which breaks down into 46,000 Btu/sq.ft./year for electrical usage and 2,000 Btu/sq.ft/year for natural gas usage. An approximate breakdown of electric consumption by end -use category is shown below. The air conditioning units utilize the largest proportion of electricity, followed by interior lighting, exterior lighting, and office equipment. ELECTRIC ENERGY USE Office and Misc Equip Interior Lighting 7% 27% Air Condition'n 46% Exterior Lighting 20% n An approximate breakdown of natural gas consumption by end -use category is shown below. The largest proportion goes toward space heating. NATURAL GAS ENERGY USE Hot Water 22% Space Heating 78% The most recent 12 months of electricity and natural gas utility data is presented in the table below. Detailed energy usage and cost histories are provided in Appendix A. Electricity Natural Gas Month Max Demand Usage Cost Usage Cost (kW) (kWh)_ (Therms) Oct 2003 211 58,768 $7,773 28 $35 Nov 2003 140 40,849 $5,052 38 $44 Dec 2003 130 41,759 $5,040 159 $150 Jan 2004 130 38,914 $4,835 317 $305 Feb 2004 130 37,406 $4,560 145 $154 j Mar 2004 164 44,457 $5,490 50 $58 Apr 2004 174 44,652 $5,495 12 $25 May 2004 211 54,176 $6,701 13 $25 Jun 2004 207 58,495 $8,998 13 $25 Jul 2004 240 69,193 $10,948 16 $27 Aug 2004 213 65,620 $10,000 15 $25 Sep 2004 229 59,236 _ $9,610 16 $27 12 Months 613,525 $84,502 822 $ 900 7 Li,ahtin2 Svstems Lighting in the office areas throughout the facility is predominantly fluorescent. The main fixture types are 3-lamp and 4-lamp, 4-foot recessed fixtures with clear prismatic lenses. Some 4-foot fixtures are equipped with open parabolic louvers. There are a limited number of 2' x 2' fixtures containing U-tube lamps, and several 3-foot fixtures as well. In the Administrative and Environmental Services original sections of the building, the fixtures contain T-12 lamps and magnetic ballasts. The 3-lamp fixtures are typically tandem -wired with 2-lamp ballasts. Most lamps are 34-watt models, although the City has been installing 40-watt enhanced color lamps on a replacement basis to improve lighting quality in some areas. It was reported that T-10 lamps had been used in the, past, but all T-10 lamps were subsequently replaced with T-12 models. Light levels in the office areas measured 45 to 50 footcandles, which is within the recommended range for office applications. The North and East additions were designed with a daylight dimming system in the interior spaces. Features of the system include skylights, ceiling -mounted photocells, and automatic dimming controls. The lighting fixtures in these areas are 3-lamp, 4-foot fixtures with T-12 lamps and tandem, 2-lamp dimming magnetic ballasts. The dimming control panels were manufactured by Lutron. The North wing was designed with five control zones, while the East wing has four. Fluorescent fixtures in the perimeter offices in the North and East wings contain T-12 lamps and non -dimming magnetic ballasts. These offices are equipped with occupancy sensor lighting controls. A number of problems have been reported with the daylight dimming system. Occupants working directly under skylights have complained of excessive brightness. To address this complaint, the City has installed mesh covers on the exteriors of some of the skylights. Operating problems have been reported with the dimming controls. The dimming system has been overridden, with lights operating at full power. Light levels in the North and East wings measured 40 to 50 footcandles in areas under the skylights with covers, and up to 190 footcandles under uncovered skylights. The Council Chambers lighting consists of incandescent and specialty lamps with dimming capability. Downlights throughout City Hall, other than in the Council Chambers, contain compact fluorescent lamps. The lobbies and hallway exhibit areas have accent lighting using MR-16 halogen lamps. Exit signs in the Administrative and Environmental Service offices were originally incandescent. They have been converted with LED retrofit kits. Exit signs in the North and East wings are fluorescent, containing two 8-watt lamps each. 0 Building exterior lighting consists of recessed downlights in walkway eaves. The original areas contained 75-watt mercury vapor lamps, while the additions were designed with 100-watt high pressure sodium fixtures. The mercury vapor fixtures have been converted to accept incandescent and compact fluorescent lamps. There is a mixture of incandescents and compact fluorescents currently installed in these fixtures. Exterior lighting includes pole -mounted HID fixtures in the open parking lots, and T-5 fluorescent fixtures mounted under the carport roofs. Exterior lighting is controlled by both photocells and time clocks. HVAC Svstems Packaged rooftop air conditioning units provide comfort cooling and heating throughout the facility. A total of 41 units are located on the roof, with cooling capacities ranging from 2 to 12.5 tons. The 21 units serving the original sections of the building are equipped with natural gas heating. The 20 units on the North and East wings are heat pumps. Ten of the units have been replaced over the last several years with high efficiency models. The inventory of rooftop units is detailed in the table on the following page. In addition to these rooftop units, there are two small split -system air conditioners serving computer equipment and electrical rooms, one each in the North and East wings. Most of the rooftop units with gas heat have minimum outside are intakes; most of the heat pumps are equipped with outside air economizers for utilization of full fresh air during cool weather periods. Two of the newer heat pumps were installed with no provision for outside air. Programmable setback thermostats control the majority of the rooftop units. There are a total of 33 programmable thermostats, manufactured by Honeywell, Robertshaw and Aprilaire. Most of the thermostats were programmed correctly at the time of our site survey, with daytime cooling temperature setpoints ranging from 75 to 78 degrees, and night setpoints of 85 degrees. The typical operating schedule was set for 6:30 AM to 5:30 PM, Monday through Friday. We also noted, though, that approximately 20 percent of the thermostats had incorrect time or temperature settings, resulting in operation during building unoccupied periods. The rooftop units without programmable thermostats are the ones serving areas with intermittent occupancy. They are equipped with either twist timers or occupancy sensors to limit operation to occupied periods. Two units serving conference rooms are controlled with occupancy sensors. Six units have manual twist timers: two serving break rooms, one in a boardroom, and three in the Council Chambers area. E Building Area ` Unit t Manufacturer I Model No. I System Type Nominal oling Capacity(Tons) 1 Carrier 48GS024040 RTU w/Gas Htg 2 2 Carrier 48GS060090 RTU w/Gas Htg 5 j 3 Carrier N/A RTU w/Gas Htg 5 Administrative ( 4 Carrier N/A RTU w/Gas Htg 7.5 Services 5 Carrier 48GSO48090 RTU w/Gas Htg 4 (9 Units) 6 Carrier 48GSO48090 RTU w/Gas Htg 4 7 Carrier 48GS060090 RTU w/Gas Htg 5 1 8 Carrier 48LH009 RTU w/Gas Htg 8.5 1 9 Carrier 48HJD008 RTU w/Gas Htg 7.5 1 1 Carrier 48HJDOOS RTU w/Gas Htg 7.5 Council I 2 Carrier 48HJD014 RTU w/Gas Htg 12.5 Chambers I 3 Carrier 48HJD014 RTU w/Gas Htg 12.5 1 (4 Units) 4 Carrier 48HJD006 RTU w/Gas Htg 5 �1 BDP 580CPU060074 RTU w/Gas Htg 5 2 Carrier 48GS060090 RTU w/Gas Htg 5 1 3 Carrier 48GS060090 RTU w/Gas Htg 5 Environmental 4 Carrier 48GS060090 RTU w/Gas Htg 5 Services 5 Carrier 48GS060090 RTU w/Gas Htg 5 (8 Units) 6 Carrier 48GS060090 RTU w/Gas Htg 5 7 Carrier 48HJD005 RTU w/Gas Htg 4 8 Carrier 4.8GSO48090 RTU w/Gas Htg 4 1 Carrier _ 50QJ004 Heat Pump 3 i 2 Carrier 50QJ006 Heat Pump 5 4 Ca rrier 50 J004 Q Heat Pum P 3 5 Carrier 50QJ005 Heat Pump 4 North Wing 6 (E) BDP 548CEX036 Heat Pump 3 (10 Units) 7 (F) BDP 548CEX060 Heat Pump 5 9 Carrier 50QJ005 Heat Pump 4 10 Carrier I 50QJ005 Heat Pump 4 11 Carrier 50QJ005 Heat Pump 4 I 12 Carrier 50QJ005 Heat Pump 4 - 13 ___--------- Carrier ..... . .... . .. .. 50HJQ005 Heat Pump 4 14 Carrier 50HJQ005 Heat Pump 4 16 Carrier 50QJ006 Heat Pump 5 17 Carrier SOHJQ004 Heat Pump 3 East Wing 18 Carrier 50NQ024 Heat Pump 2 (10 Units) ( 19 Carrier 50NQ024 Heat Pump , 2 20 Carrier 50NQ024 Heat Pump 2 21 Carrier 50QJ004 Heat Pump 3 j 22 Carrier 50HJQ004 Heat Pump 3 23 Carrier 50QJ004 Heat Pump l 3 Total (41 Units) _ — i I—� J 194 L�1, Miscellaneous EnerQv Svstems Several years ago, the City installed a solar photovoltaic system on a carport roof in the parking lot adjacent to the building. The system consists of 192 Siemens SM50 panels, with a nameplate capacity of 50 watts each, and a 15 kW inverter. The actual output averages only 4.7 kW, however, due to shading from trees located throughout the carport area. Another carport, located on the North end of the site, was built with a future solar installation in mind. The structure was designed to handle solar panels, and conduit was installed from the carport to the electrical yard as well. This carport is free from shading, since there are no trees in the area. Other miscellaneous energy systems at City Hall include several gas -fired water healers providing domestic hot water to the facility; general office equipment; and some kitchen equipment and vending machines in several break rooms. 11 Lighting Project #1: Compact Fluorescent Exterior Lamps Proiect Description The recessed downlights in exterior walkway eaves that were converted from the original mercury vapor fixtures contain a mixture of incandescent and compact fluorescent lamps. The incandescent lamps used are typically 90-watt PAR38 floodlamps or A -line lamps, and there are a variety of compact fluorescent models. It was reported that some of the compact fluorescents had burned out prematurely and were subsequently replaced with the incandescents. We recommend that the incandescent lamps be replaced with high quality 26-watt compact fluorescent lamps that will provide the longevity expected of these lamps. The compact fluorescent retrofit will reduce electric consumption, and it will reduce maintenance costs because the fluorescent lamps will have a much longer life than the incandescent lamps they replace. Implementation Scope of Work 1. Replace existing incandescent lamps in exterior eave fixtures with 26-watt compact fluorescent lamps (approximately 20 lamps total). Analvsis Summary Peak Annual Annual Demand Savings Electrical Natural Gas (kW) Savings Savings (kWh) (Gallons) 0 5,256 0 Annual Installation Simple Cost Savings Cost Payback (years) S451 I $202 I 0.4 Note: Installation cost is based on work performed by City personnel. 12 Lighting Project #2: T-8 Lamps and Electronic Ballasts Proi ect Description The existing T-12 lamps and magnetic ballasts can be replaced with the latest generation T-8 lamps and electronic ballasts to greatly reduce fixture wattage while maintaining light levels and improving the quality of the lighting system. The combination of 28-watt T-8 lamps and high efficiency, low output electronic ballasts will draw 44 watts per 2-lamp ballast. Currently, the fixtures with 34-watt T-12 lamps and magnetic ballasts draw 72 watts per 2-lamp ballast; the ones with 40-watt T-12 lamps draw 86 watts; and the dimmable fixtures with 34-watt lamps require 84 watts per 2-lamp ballast at full power. This project includes retrofitting the dimming fixtures in the North and East wings with T-8 lamps and non -dimming electronic ballasts, which will eliminate the daylight dimming system. An alternative approach would be to install dimming electronic ballasts in these fixtures to maintain the capability for daylight dimming control. However, the Lutron control panels would need to be replaced as well, since the existing components in these panels are not compatible with electronic ballasts. Due to the much higher cost of this approach, the operating problems reported with the skylights and the existing dimming system, and the dramatic wattage reduction achievable with non -dimming ballasts, we recommend abandoning the daylight dimming system, as presented in this project. Some rewiring of the former dimming fixtures will be necessary to provide local bi- level switching control. ImDlementation Scope of Work Remove T-12 lamps and standard magnetic ballasts from existing 4-foot fluorescent fixtures. Wipe clean fixture interiors. Install 28-watt T-8 lamps and high efficiency, low output electronic ballasts in existing fixtures (approximately 925 4-foot lamps, 3 1-lamp ballasts, 458 2-lamp ballasts, 2 3-lamp ballasts total). 2. Remove T-12 lamps and dimming magnetic ballasts from existing 4-foot fluorescent fixtures. Wipe clean fixture interiors. Install 28-watt T-8 lamps and high efficiency, low output electronic ballasts in existing fixtures (approximately 276 4-foot lamps, 138 2-lamp ballasts total). 3. Rewire circuits on the former dimming fixtures to provide local bi-level switching control. This will require additional conduit and wiring, circuit breakers and wall switches. 4. Remove T-12 U-tube lamps and magnetic ballasts from existing 2' x 2' fixtures. Convert fixtures to accept straight 2-foot T-8 lamps with new white reflectors. Install two 2-foot T-8 lamps and an electronic ballast in each fixture (approximately 46 2-foot lamps, 23 2-lamp ballasts total). 5. Remove T-12 lamps and magnetic ballasts from existing 3-foot fluorescent fixtures. Wipe clean fixture interiors. Install 3-foot T-8 lamps and electronic ballasts in existing fixtures (approximately 21 3-foot lamps, 9 2-lamp ballasts, 3 1-lamp ballasts total). 13 6. Properly dispose of removed fluorescent lamps and ballasts. Existing Fixture Type Approximate Fixture Retrofit Measure Qty - 4-ft, 4-lamp 65 Replace lamps and ballasts with 24amp electronic ballasts 4-ft, 3-lamp tandem 184 Replace lamps and ballasts with 24amp electronic ballasts 4-ft, 3-lamp tandem 92 Replace lamps and ballasts with 2-lamp dimming electronic ballasts; rewire circuits 4-ft, 3-lamp non -tandem 2 Replace lamps and ballasts with 3-lamp electronic ballasts 4-ft, 2-lamp 52 Replace lamps and ballasts with 2-lamp electronic ballasts 4-ft, 1-lamp 3 Replace lamps and ballasts with 1-lamp electronic ballasts 34, 2-lamp 9 Replace lamps and ballasts with 2-lamp electronic ballasts 3-ft, 1-lamp 3 Replace lamps and ballasts with 1-lamp electronic ballasts 2' x 2' U-tube 23 Convert to 2-ft T-8 lamps, install 2-lamp electronic ballasts and white reflectors Total Fixtures 433 Analvsis Summary Peak Annual Annual Demand Savings Electrical Natural Gas Annual Installation Simple (kW) Savings Savings Cost Savings Cost Payback (kWh) (Gallons) (years) 20.9 ' 58,514 I 0 I $8,325 I $39,070 I 4.7 With SCE Express Efficiency Rebate I $8,325 $33,715 I 4.0 Notes: 1. Installation cost is based on work performed by a lighting contractor. 2. Express Efficiency Rebate of $5,354 based on 2004 program rates. 14 Lighting Project #3: LED Exit Signs Proiect Description The exit signs in the North and East wings are each lit by two 8-watt fluorescent lamps, with a total power draw, including ballasts, of 21 watts per fixture. Replacing the existing exit signs with LED exit signs, which consume less than 4 watts each, will reduce both peak electric demand and consumption. Maintenance effort and costs will also be reduced because the LED's should last at least 10 years before requiring replacement. Implementation Scope of Work 1. Remove the existing fluorescent exit signs and install new LED exit signs in their place. The new exit signs should be equipped with emergency battery backup, similar to the existing signs (8 exit signs total). Analvsis Summary Peak Annual Annual Demand Savings Electrical Natural Gas Annual (kW) Savings Savings Cost Savings (kWh) (Gallons) 0.1 I 1,191 I 0 ( $123 Installation Simple Cost Payback (years) $717 I 5.8 Note: Installation cost is based on work performed by a lighting contractor. 15 HVAC Project #1: Thermostat Programming Proiect Description City Hall rooftop units are controlled with 33 programmable thermostats. During the site survey, we noted that approximately 20 percent of the thermostats were not programmed correctly. Problems included the following: • Wrong day or time setting • Incorrect unoccupied temperature setpoints • Operation on weekends This situation is causing energy waste, since some of the rooftop units are operating when the building is unoccupied. The thermostats should be reprogrammed with proper time and day settings, schedules that match occupancy periods, and a cooling setback temperature of 85 degrees. Building occupants can use the temporary override feature to change temperature settings but should not alter the basic programming. All thermostats should be checked routinely to ensure that the proper programs are maintained on an on -going basis. The savings calculation for this project is based on reprogramming six thermostats that were observed with significant program deviations. Implementation Scope of Work 1. Review programming instructions for the Honeywell, Robertshaw and Aprilaire thermostats. 2. Program all thermostats with proper day and time, occupancy schedules for weekdays and weekends, and setback temperatures of 55 degrees for heating and 85 degrees for cooling. 3. Instruct occupants on the use of the override feature for adjusting temperature settings without changing the basic programming. 4. Establish a routine for checking the thermostats on a monthly or quarterly basis. Analvsis Summary Peak Annual Annual Demand Savings Electrical Natural Gas Annual Installation Simple (kW) Savings Savings Cost Savings Cost Payback (kWh) (Therms) (years) 0 I 20,537 I 0 I $1,764 I $0 I Immediate Note: There is no installation cost for this project, based on City personnel performing the work. 16 Solar Project #1: Solar PV System Proiect Description The North carport was built with structural capacity for future installation of.solar photovoltaic panels. The necessary electrical infrastructure was also installed. There is no potential shading in the area. The existing electric yard has space for additional inverter capacity and transformers. The existing carport PV system also has space to accommodate additional panels, and the City has an inventory of panels that have already been purchased. A 40 kWnc solar PV system can be installed on the North carport to provide solar power in addition to the existing PV system at City Hall. This system sizing will provide approximately 27.2 kWAc actual power to the facility. In addition, the existing PV system can be expanded with the installation of 10 kWDc of solar panels that the City already owns. This addition is estimated to provide 4.7 kWAc actual power, based on the performance of the existing panels. The combined 50 kWDc size of the new system was selected based on existing infrastructure and overall payback considerations. The savings calculation for this project was developed using the PVWatts v.2 software provided by the National Renewable Energy Laboratory, using Palm Desert solar data. Implementation Scope of Work 1. Design and specify a new 40 kWDc solar PV system for the North carport. Install the new PV panels on the North carport roof. 2. Reconfigure the existing PV system and carport racks to accommodate an additional 10 kWDc of panels from the City inventory. Install these panels on the carport roof. 3. Install wiring in existing conduit to the electrical yard. 4. Install inverters and transformers in the electrical yard. 5. Commission the PV system to ensure proper operation and maximum power production. 17 Analvsis Summary Peak Annual Annual Demand Savings Electrical Natural Gas Annual Installation Simple (kW) Savings Savings Cost Savings Cost Payback (kWh) (Therms) (years) 31.9 I 63,718 ( 0 I $8,547 I $290,000 I 33.9 With Self Generation Incentive I $8,547 I $162,500 I 19.0 Notes: 1. Installation cost is based on turnkey contractor pricing at $6.50 per nameplate watt for the new system, and $3.00 per nameplate watt for the addition to the existing system. 2. Self Generation Incentive of $127,500 based on 2005 expected rate of $3.00 per AC watt. In ADDITIONAL ISSUES The following items cover additional issues that were investigated in the course of this study. These items may warrant further action immediately or in the future. Rooftop Unit Minimum Outside Air Rooftop heat pump units 13 and 14 on the East wing roof were installed with no outside air. These units should be equipped with minimum outside air intakes to provide ventilation air and ensure adequate indoor air quality in the spaces they serve. Older Rooftop Unit Replacement The City has already replaced ten of the rooftop units with high efficiency models over the past several years. While wholesale replacement of the remaining older units cannot be justified on the basis of energy savings alone, the City should continue to replace the units as funds become available. Enemy Management System We investigated the feasibility of installing a central energy management system to control the rooftop HVAC units, in lieu of the existing programmable thermostats, twist rimers and occupancy sensors. A central energy management system could provide demand shedding of the units to reduce peak demand, central scheduling control, and temperature reset to allow space temperatures to drift upward on peak days. The incremental savings beyond the capability of the existing controls was not significant enough to justify the cost of a central system. Review of historical interval electric data indicated that the potential for demand shedding through cycling of the units was limited. The potential for upward drift of space temperatures is also very limited, because current setpoints are already 77 to 78 degrees in many areas. Exterior Liahtina Control Exterior lighting represents a significant electrical load at the facility. During our site survey, it appeared that the photocell and time clock controls were functioning properly. These controls should continue to be checked on a regular basis to prevent unnecessary operation of the exterior lighting fixtures when ambient lighting is available. Occunancv Sensors The facility has occupancy sensor lighting controls in perimeter office areas in the North and East wings. There did not appear to be significant spaces elsewhere in the facility that would be good candidates for further application of occupancy sensor controls. Irrigation Pumv As part of this study, we were asked to investigate the potential for retrofit of the irrigation pump located adjacent to the City Hall site. During the survey, it was determined that the irrigation pump was not powered from City Hall's electric service, but rather was under the Parks Department electric account. We therefore did not pursue an evaluation of pump retrofit opportunities. Rol APPENDIX A HISTORICAL ENERGY USE A-1 APPENDIX B ENGINEERING CALCULATIONS MANUFACTURERS' PRODUCT LITERATURE Sample product literature applicable to the recommended projects is provided in this Appendix. The literature is included here for illustrative purposes only. Neither the California Energy Commission nor Servidyne endorse any particular manufacturers or products. C-1