HomeMy WebLinkAboutCivic Center Solar Systm Performance & Cost Savings\it S CITY OF PALM DESERT CITY MANAGERS OFFICE STAFF REPORT TO: Honorable Mayor and City Council Members SUBJECT: CIVIC CENTER PHOTOVOLTAIC SOLAR SYSTEM PERFORMANCE AND COST SAVINGS SUBMITTED BY: Patrick Conlon, Director of Office of Energy Management DATE: July 13, 2006 As requested at the June 22, 2006 City Council meeting, staff has prepared a report on the performance of the Civic Center Photovoltaic (P.V.) Solar System. This information was gathered from the data logging capabilities, built into the system's inverter, and compared to the Southern California Edison (SCE) electrical billing for the Civic Center. In the last 12 months, the P.V. system generated 6,864 kWh of electrical power, which is fed into our main electrical service equipment. This power was produced from 10 a.m. to 4 p.m., during SCE's peak demand time period. The cost savings to the City in the last year was approximately $4,470. The cost to install this system onto the carports was $84,000. Using SCE's current electrical rates and with a continued annual savings of $4,470, the simple pay back for this P.V. system is 18.7 years. It should be noted that due to the shading of the P.V. panels from the date palms, located in the center of the carports, the system is producing leas than one-half of it's capacity, thus a longer pay back period. If there are any questions, please contact Pat Conlon. Submitted by: PA---o.„,____ Patrick Conlon Director of Office of Energy Management G: lCityMgrUane StanleylWord FileslPat ConlonlReports & Memos\PV system Council report 7-13-06.doc `CITY COUNCIL ACTION: APPROVED DENIED RECEIVED rkaa OTHER MEETIN DATE !'�� AYES: (ae rrvil K�Pa 11 4 PLe 1w L~- G44-fLd NOES: k-Y'( ABSENT:_brY ABSTAIN :.„..a/nP- � �� ran BY:. Original on File with City Clerk's Office