HomeMy WebLinkAbout2022 California Green Residential Mandatory Measures ChecklistPage 1 of 10
Chapter 3 – Additions and Alterations Scope
301.1.1
• Applies to additions and alterations of residential buildings where the addition or alteration increases
the building’s conditioned area, volume, or size.
• Requirements only apply within the specific area of the addition or alteration.
• After January 1, 2014, all residential buildings undergoing permitted alterations, additions, or
improvements shall replace non-compliant plumbing fixtures with water-conserving plumbing fixtures
(Civil Code §1101.1).
Division 4.106 – Planning and Design (Site Development)
SECTION SCOPE REQUIREMENTS
4.106.2
Storm Water
Drainage
&
Retention
(During Construction) Projects which disturb less than one acre of
soil and are not part of a larger common plan of development which
in total disturbs one acre or more, shall manage storm water
drainage during construction.
Coordinate
with
Public Works
4.106.3
Grading
&
Paving
Construction plans shall indicate how the site grading or drainage
system will manage all surface water flows to keep water from
entering buildings. Exceptions: Additions and alterations which do
not alter the existing drainage path.
Demonstrate
On
Site Plan
Division 4.106 – Planning and Design (EV Charging Requirements)
4.106.4 New
Construction
• Shall comply with Section 4.106.4.1or 4.106.4.2, or 4.106.4.3 for future installation and
use of EV chargers.
• Electric vehicle supply equipment (EVSE) shall be installed in accordance with the
California Electrical Code, Article 625.
Exceptions: on a case-by-case basis as determined by the AHJ that EV charging and infrastructure
are not feasible based upon one or more:
1. Where there is no local power supply, or the local utility is unable to supply adequate power.
2. Evidence substantiating adding the infrastructure of EVSE may adversely impact costs.
3. ADU or JADU without additional parking.
4.106.4.1
&
4.106.4.1.1
1 & 2 - Family
Dwellings
Townhouses
with
Attached
private
garages.
- Install a listed raceway to accommodate a dedicated 208/240-volt branch circuit for each
dwelling unit.
- Raceway shall not be less than trade size 1 (nominal 1-inch inside diameter).
- Raceway shall originate at the main service or subpanel and terminate into a listed
cabinet, box, or other enclosure in close proximity to the proposed location of an EV
charger.
- Raceways are required to be continuous at enclosed, inaccessible, or concealed areas
and spaces.
Service panel and/or subpanel shall provide capacity to install a 40A minimum dedicated
branch circuit and space(s) reserved to permit installation of a branch circuit overcurrent
protective device. Exception: A raceway is not required if a minimum 40-ampere 208/240-volt dedicated EV
branch circuit is installed in close proximity to the proposed location of an EV charger at the time of original
construction in accordance with the California Electrical Code.
- Service panel or subpanel circuit directory shall identify the overcurrent protective device space(s)
reserved for future EV charging as “EV CAPABLE.” The raceway termination location shall be
permanently and visibly marked as “EV CAPABLE.”
CITY OF PALM DESERT
Building & Safety Division
73-510 Fred Waring, Palm Desert, CA (760) 776-6420 Website: https://www.palmdesert.gov
2022 CALIFORNIA GREEN BUILDING RESIDENTIAL
MANDATORY MEASURES CHECKLIST (#BLDG-CKL-23-0011)
Page 2 of 10
Division 4.106 – Planning and Design (EV Charging Requirements)
4.106.4.2 (N)Multi-Family Dwellings
Hotel/Motels
Residential Parking Facilities
When parking is provided, parking spaces shall meet the requirements of
Sections 4.106.2.1 and 4.106.4.2.2. Calculations for spaces shall be rounded
up to the nearest whole number.
A parking space served by an EVSE or designated as a future EV charging
space shall count as at least one standard automobile parking space for the
purpose of complying with any applicable minimum parking space
requirements by the City of Palm Desert.
SECTION SCOPE REQUIREMENTS
4.106.4.2.1
(1) & (2)
Multifamily
Projects
with
LESS THAN
20
Dwelling
Units
____
Hotels/Motels
with
LESS THAN
20
Sleeping
Units
Guest Rooms
(1) EV Capable: Ten (10) percent of the total number of parking spaces on a building site,
provided for all types of parking facilities, shall be electric vehicle charging spaces (EV
spaces) capable of supporting future Level 2 EVSE. Electrical Load calculations shall
demonstrate the service panel capacity, including all equipment have the sufficient
capacity to simultaneously charge all EVs at a minimum of 40A. Service Panels and/or
subpanels shall label the OCPD reserved for future EV use and “EV CAPABLE.”
Exceptions:
1. When EV chargers (Level 2 EVSE) are installed in a number equal to or greater than the required number
of EV capable spaces.
2. When EV chargers (Level 2 EVSE) are installed in a number less than the required number of EV capable
spaces, the number of EV capable spaces required may be reduced by a number equal to the number
of EV chargers installed.
Notes:
- Construction documents shall show locations of future EV spaces.
- There is no requirement for EV spaces to be constructed or available until receptacles
for EV charging or EV chargers are installed for use.
(2) EV Ready: Twenty-five (25) percent of the total number of parking spaces shall be
equipped with low power Level 2 EV charging receptacles. For multifamily parking
facilities, no more than one receptacle is required per dwelling unit when more than one
parking space is provided for use by a single dwelling unit.
Exception: Areas of parking facilities served by parking lifts.
4.106.4.2.2
(1) & (2)
Multifamily
Projects
with
20 OR MORE
Dwelling Units
And
Hotels/Motels
with
20 OR MORE
Sleeping Units
Guest Rooms
(1) EV Capable: Ten (10) percent of the total number of parking spaces on a building site,
provided for all types of parking facilities, shall be electric vehicle charging spaces (EV
spaces) capable of supporting future Level 2 EVSE. Electrical Load calculations shall
demonstrate the service panel capacity, including all equipment have the sufficient
capacity to simultaneously charge all EVs at a minimum of 40A. Service Panels and/or
subpanels shall label the OCPD reserved for future EV use and “EV CAPABLE.”
The service panel or subpanel circuit directory shall identify the overcurrent protective device
space(s) reserved for future EV charging purposes as "EV CAPABLE" in accordance with the California
Electrical Code.
Exception: When EV chargers (Level 2 EVSE) are installed in a number greater than five (5) percent of
parking spaces required by Section 4.106.4.2.2, Item 3, the number of EV capable spaces required
may be reduced by a number equal to the number of EV chargers installed over the five (5) percent
required.
Notes:
- Construction documents shall show locations of future EV spaces.
- There is no requirement for EV spaces to be constructed or available until receptacles
for EV charging or EV chargers are installed for use.
(2) EV Ready: Twenty-five (25) percent of the total number of parking spaces shall be
equipped with low power Level 2 EV charging receptacles. For multifamily parking
facilities, no more than one receptacle is required per dwelling unit when more than one
parking space is provided for use by a single dwelling unit.
Exception: Areas of parking facilities served by parking lifts.
Page 3 of 10
Division 4.106 – Planning and Design (EV Charging Requirements)
SECTION SCOPE REQUIREMENTS
4.106.4.2.2
(3)
Multifamily
Projects
and
Hotels/Mote
ls with
20 or MORE
Dwelling
Units,
Sleeping
Units, or
Guest
Rooms
(3) EV Chargers: Five (5) percent of the total number of parking spaces shall be
equipped with Level 2 EVSE. Where common use parking is provided, at least
one EV charger shall be located in the common use parking area and shall be
available for use by all residents or guests:
- When low power Level 2 EV charging receptacles or Level 2 EVSE are installed
beyond the minimum required, an automatic load management system (ALMS)
may be used to reduce the maximum required electrical capacity to each space
served by the ALMS.
- The electrical system and any on-site distribution transformers shall have
sufficient capacity to deliver at least 3.3 kW simultaneously to each EV charging
station (EVCS) served by the ALMS.
- The branch circuit shall have a minimum capacity of 40 amperes, and
installed EVSE shall have a capacity of not less than 30 amperes. ALMS shall
not be used to reduce the minimum required electrical capacity to the
required EV capable spaces.
4.106.4.2.2.1
Electric vehicle charging stations required by Section 4.106.4.2.2.1.2, Item 3, shall comply
with Section 4.106.4.2.2.1.1.
Exception: Electric vehicle charging stations serving public accommodations, public housing, motels, and
hotels shall not be required to comply with this section. See California Building Code, Chapter 11B, for
applicable requirements.
4.106.4.2.2.1.1
EV
Charging
Space
(Locations)
EVCS shall comply with at least one of the following options:
1. The charging space shall be located adjacent to an accessible parking space
meeting the requirements of the California Building Code, Chapter 11A, to allow
use of the EV charger from the accessible parking space.
2. The charging space shall be located on an accessible route, as defined in the
California Building Code, Chapter 2, to the building.
Exception: Electric vehicle charging stations designed and constructed in compliance with
the California Building Code, Chapter 11B, are not required to comply with Section
4.106.4.2.2.1.1 and Section 4.106.4.2.2.1.2, Item 3.
4.106.4.2.2.1.2
EV
Charging
Space
(Dimensions)
EV spaces shall be designed to comply with the following:
1. The minimum length of each EV space shall be 18 feet.
2. The minimum width of each EV space shall be 9 feet.
3. One in every 25 EV spaces, but not less than 1, shall also have an 8-foot-wide
minimum aisle. A 5-foot minimum aisle shall be permitted provided the minimum
width of the EV space is 12 feet.
(3a) - Surface slope for this EV space and aisle shall not exceed 1 unit vertical in
48 units horizontal (2% slope) in any direction.
4.106.4.2.2.1.3 Accessible
EV Spaces
In addition to the requirements in Sections 4.106.4.2.2.1.1 and 4.106.4.2.2.1.2, all EVSE,
when installed, shall comply with the accessibility provisions for EV chargers in the
California Building Code, Chapter 11B. EV ready spaces and EVCS in multifamily
developments shall comply with California Building Code, Chapter 11A, Section 1109A.
Page 4 of 10
Division 4.106 – Planning and Design (EV Charging Requirements)
SECTION SCOPE REQUIREMENTS
4.106.4.2.3
(1)
Single EV
Space
(Required)
• Install listed raceway capable of accommodating a 208/240-volt dedicated
branch circuit.
•
• The raceway shall originate at the main service or subpanel and shall
terminate into a listed cabinet, box, or enclosure in proximity to the location
or proposed location of the EV space.
•
• Construction documents shall identify the raceway termination point,
receptacle, or charger location, as applicable.
•
• The service panel and/or subpanel shall provide capacity to install a 40A
minimum branch circuit and space(s) reserved to permit installation of a
branch circuit overcurrent protective device.
•
• Exception: A raceway is not required if a minimum 40-ampere 208/240-volt
dedicated EV branch circuit is installed in close proximity to the location or
the proposed location of the EV space, at the time of original construction in
accordance with the California Electrical Code.
4.106.4.2.3
(2)
Multiple EV
Spaces
(Required)
• Construction documents shall indicate raceway termination point and proposed
location of future EV spaces and EV chargers. Construction documents shall
also provide information on amperage of future EVSE, raceway method(s),
wiring schematics (SLD) and load calculations to verify electrical panel service
capacity and electrical system, including any on-site distribution transformer(s),
have sufficient capacity to simultaneously charge all EVs at all required EV
spaces at full rated amperage of ESVE.
• Plan design shall be based upon a 40A minimum branch circuit.
• Required raceways and related components planned to be installed
underground, enclosed, inaccessible or in concealed areas and spaces shall
be installed at the time of original construction.
Exception: A raceway is not required if a minimum 40-ampere 208/240-volt dedicated EV branch
circuit is installed near the location or the proposed location of the EV space, at the time of
original construction in accordance with the California Electrical Code.
4.106.4.2.4 Identification
The service panel or subpanel circuit directory shall identify the overcurrent
protective device space(s) reserved for future EV charging purposes as “EV
CAPABLE” in accordance with the California Electrical Code.
4.106.4.2.5
Electric
Vehicle
Ready Space
Signage
Electric vehicle ready spaces shall be identified by signage or pavement
markings, in compliance with Caltrans Traffic Operations Policy Directive 13-01
(Zero Emission Vehicle Signs and Pavement Markings) or its successor(s).
4.106.4.3
EV Charging
Add/Alters
of
Parking
Facilities
(E)
Multifamily
Buildings
When new parking facilities are added, or electrical systems or lighting of existing
parking facilities are added or altered and the work requires a building permit, ten
(10) percent of the total number of parking spaces added or altered shall be electric
vehicle charging spaces (EV spaces) capable of supporting future Level 2 EVSE.
Notes:
- Construction documents are intended to demonstrate the project's capability and capacity for
facilitating future EV charging.
- There is no requirement for EV spaces to be constructed or available until EV chargers are
installed for use.
Page 5 of 10
Division 4.2 – Energy Efficiency (Scope)
4.201.1 For the purposes of mandatory energy efficiency standards in this code, the California Energy
Commission will continue to adopt mandatory standards.
Division 4.303 – Water Efficiency and Conservation (Indoor Use)
4.301.1 The provisions of this chapter shall establish the means of conserving water used indoors,
outdoors and in wastewater conveyance.
SECTION SCOPE REQUIREMENTS
4.303 Fixtures and
Fittings
Plumbing fixtures (water closets and urinals) and fittings (faucets and showerheads)
shall comply with Sections 4.303.1.1, 4.303.1.2, 4.303.1.3 and 4.303.1.4.
4.303.1.1 Water
Closets
The effective flush volume of all water closets shall not exceed 1.28 gallons per
flush. Tank-type water closets shall be certified to the performance criteria of the
US EPA WaterSense Specification for Tank-type Toilets.
Note: The effective flush volume of dual flush toilets is defined as the composite, average
flush volume of two reduced flushes and one full flush.
Division 4.303 – Water Efficiency and Conservation (Indoor Use)
SECTION SCOPE REQUIREMENTS
4.303.1.2 Urinals
The effective flush volume of wall-mounted urinals shall not exceed 0.125 gallons
per flush. The effective flush volume of all other urinals shall not exceed 0.5 gallons
per flush.
4.303.1.3.1 Single
Showerheads
Showerheads shall have a maximum flow rate of not more than 1.8 gallons per
minute at 80 psi. Showerheads shall be certified to the performance criteria of the
US EPA WaterSense Specification for Showerheads.
4.303.1.3.2 Multiple
Showerheads
(One-Shower)
When a shower is served by more than one showerhead, the combined flow rate of
all showerheads and/or other shower outlets controlled by a single valve shall not
exceed 1.8 gallons per minute at 80 psi, or the shower shall be designed to allow
only one shower outlet to be in operation at a time.
Note: A hand-held shower shall be considered a showerhead
4.303.4.1
Faucets
Residential
Lavatory
The maximum flow rate of residential lavatory faucets shall not exceed 1.2 gallons
per minute at 60 psi. The minimum flow rate of residential lavatory faucets shall not
be less than 0.8 gallons per minute at 20 psi
4.303.1.4.2
&
4.303.4.3
Faucets
Common Use
Public Use
Lavatory
&
Metering
The maximum flow rate of lavatory faucets installed in common and public use areas
(outside of dwellings or sleeping units) in residential buildings shall not exceed 0.5
gallons per minute at 60 psi.
Metering faucets when installed in residential buildings shall not deliver more than
0.2 gallons per cycle.
4.303.1.4.4 Kitchen
Faucets
The maximum flow rate of kitchen faucets shall not exceed 1.8 gallons per minute
at 60 psi. Kitchen faucets may temporarily increase the flow above the maximum
rate, but not to exceed 2.2 gallons per minute at 60 psi and must default to a
maximum flow rate of 1.8 gallons per minute at 60 psi.
Note: Where complying faucets are unavailable, aerators or other means may be
used to achieve reduction
4.303.2
Submeters for Multifamily Buildings/Dwelling Units
Mixed-Use Residential
Commercial Buildings
Submeters shall be installed to measure water
usage of individual rental dwelling units in
accordance with the California Plumbing Code.
Page 6 of 10
Division 4.304 – Water Efficiency and Conservation (Outdoor Use)
4.304.1
Residential developments shall comply with a local water efficient landscape ordinance or the
current California Department of Water Resources' Model Water Efficient Landscape Ordinance
(MWELO), whichever is more stringent.
Notes:
The Model Water Efficient Landscape Ordinance (MWELO) is located in the California Code of Regulations,
Title 23, Chapter 2.7, Division 2. MWELO and supporting documents, including a water budget calculator,
are available at: https://www.water.ca.gov/
Division 4.401 – Material Conservation & Resource Efficiency
4.401.1
The provisions of this chapter shall outline means of achieving material conservation and
resource efficiency through protection of buildings from exterior moisture; construction waste
diversion; employment of techniques to reduce pollution through recycling of materials; and
building commissioning or testing, adjusting, and balancing.
SECTION SCOPE REQUIREMENTS
4.406.1 Rodent
Proofing
Annular spaces around pipes, electric cables, conduits, or other openings in
sole/bottom plates at exterior walls shall be closed with cement mortar, concrete
masonry, or a similar method acceptable to the enforcing agency to prevent
passage of rodents.
Division 4.408 – Material Conservation & Resource Efficiency
SECTION SCOPE REQUIREMENTS
4.408.1
4.408.2
4.408.3
4.408.4
4.408.5
Construction
Waste
Reduction
The City of Palm Desert adopted the State of California’s 2022 Green Building
Standards Code as part of Palm Desert Municipal Ordinance 1388. This Code and
Ordinance requires that builders/contractors recycle and/or salvage a minimum of
65% of the non-hazardous construction and demolition debris or meet a local
construction and demolition waste management ordinance, whichever is more
stringent.
This applies to all additions or alterations of existing residential buildings where the
addition or alteration increases the building’s conditioned area, volume, or size. It
also applies to newly constructed non-residential buildings, building additions of
1,000 square feet or greater, and/or building alterations with a permit valuation of
$200,000 or above.
Failure to comply with Ordinance 1388 may result in fines AND/OR penalties.
Failure to provide documentation from salvage, recycling and waste facilities may
result in a final inspection not being issued.
Exceptions: 1. Excavated soil and land-clearing debris.
2. Alternative waste reduction methods developed by working with local enforcing agencies if diversion or recycle facilities capable of compliance with this item do not exist or are not located reasonably close to the jobsite.
Documentation shall be provided to the enforcing agency which demonstrates
compliance with Section 4.408.2, Items 1 through 5, Section 4.408.3 or Section
4.408.4.
Page 7 of 10
Division 4.501 – Environmental Quality
4.501.1
The provisions of this chapter shall outline means of reducing the quantity of air contaminants that
are odorous, irritating and/or harmful to the comfort and well-being of a building's installers,
occupants, and neighbors.
4.503.1 Fireplaces
Any installed gas fireplace shall be a direct-vent sealed-combustion type. Any installed
woodstove or pellet stove shall comply with US EPA New Source Performance
Standards (NSPS) emission limits as applicable and shall have a permanent label
indicating they are certified to meet the emission limits. Woodstoves, pellet stoves and
fireplaces shall also comply with applicable local ordinances
Division 4.504 – Environmental Quality – Pollutant Control
4.504.1
Protection
of
Mechanical
Equipment
At the time of rough installation, during storage on the construction site and until final
startup of the heating, cooling and ventilating equipment, all duct and other related air
intake and distribution component openings shall be covered. Tape, plastic, sheet
metal or other methods acceptable to the enforcing agency to reduce the amount of
water, dust and debris entering the system may be used.
4.504.2.1
Adhesives
Sealants
Caulks
Adhesives, sealants, and caulks used on the project shall meet the requirements of
the following standards unless more stringent local or regional air pollution or air quality
management district rules apply:
1. Adhesives, adhesives bonding primers, adhesive primers, sealants, sealant
primers, and caulks shall comply with local or regional air pollution control or air
quality management district rules where applicable, or SCAQMD Rule 1168
VOC limits, as shown in Tables 4.504.1 or 4.504.2 as applicable. Such products
shall also comply with Rule 1168 prohibition on the use of certain toxic
components (chloroform, ethylene, dichloride, methylene chloride,
perchloroethylene, and trichloroethylene), except for aerosol products as
specified in subsection 2 below.
2. Aerosol adhesives, and smaller unit sizes of adhesives, and sealant or caulking
compounds (in units of product, less packaging, which do not weigh more than
one pound and do not consist of more than 16 fluid ounces) shall comply
statewide VOC standards and other requirements, including prohibitions on use
of certain toxic compounds, of California Code of Regulations, Title 17,
commencing with Section 94507
Division 4.410 – Building Maintenance & Operation
SECTION SCOPE REQUIREMENTS
4.410.1
Operations &
Maintenance
Manual
At the time of final inspection, a manual, compact disc, web-based reference, or other
media acceptable to the enforcing agency which covers 12 specific subject areas shall
be placed in the building.
4.410.2 Recycling by
Occupants
Where 5 or more multifamily dwelling units are constructed on a building site, provide
readily accessible area(s) that serves all buildings on the site and is identified for the
depositing, storage, and collection of non-hazardous materials for recycling, including
(at minimum) paper, corrugated cardboard, glass, plastics, organic waste, and metals
or meet a lawfully enacted local recycling ordinance, if more restrictive.
Page 8 of 10
Division 4.504 – Environmental Quality – Pollutant Control
SECTION SCOPE REQUIREMENTS
4.504.2.2
Paints
And
Coatings
Architectural paints and coatings shall comply with VOC limits in Table 1 of the ARB
Architectural Suggested Control Measures as shown in Table 4.504.3 unless the
more stringent local limits apply. The VOC content limit for coatings that do not meet
the definitions for the specialty coatings categories listed in Table 4.504.3 shall be
determined by classifying the coating as Flat, Nonflat, or Nonflat-High Gloss coating,
based on its gloss as defined in subsections 4.21, 4.36, and 4.37 of the 2007
California Air Resources Board, Suggested Control Measure, and the corresponding
Flat, Nonflat or Nonflat-high Gloss VOC limit in Table 4.504.3 shall apply.
4.504.2.3
Aerosol
Paints and
Coatings
Aerosol paints and coatings shall meet the Product-Weighted MIR Limits for ROC in
Section 94522(a)(2) and other requirements, including prohibitions on use of certain
toxic compounds and ozone depleting substances, in Section 94522(e)(1) and (f)(1)
of the CCR, Title 17, commencing with Section 94520.
4.504.3 Carpet
Systems
All carpet installed in the building interior shall meet the requirements of the
California Department of Public Health, "Standard Method for the Testing and
Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using
Environmental Chambers," Version 1.2, January 2017 (Emission testing method for
California Specification 01350).
See California Department of Public Health's website for certification programs and
testing labs.
https://www.cdph.ca.gov/Programs/CCDPHP/DEODC/EHLB/IAQ/Pages/VOC.aspx
4.504.3.1 Carpet
Cushion
All carpet cushion installed in the building interior shall meet the requirements of
the California Department of Public Health, "Standard Method for the Testing and
Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using
Environmental Chambers," Version 1.2, January 2017 (Emission testing method for
California Specification 01350).
See California Department of Public Health's website for certification programs and
testing labs.
https://www.cdph.ca.gov/Programs/CCDPHP/DEODC/EHLB/IAQ/Pages/VOC.aspx
4.504.3.2 Carpet
Adhesive All carpet adhesives shall meet the requirements of Table 4.504.1.
4.504.4
Resilient
Flooring
Systems
Where resilient flooring is installed, at least 80 percent of floor area receiving
resilient flooring shall meet the requirements of the California Department of Public
Health, "Standard Method for the Testing and Evaluation of Volatile Organic
Chemical Emissions from Indoor Sources Using Environmental Chambers,"
Version 1.2, January 2017 (Emission testing method for California Specification
01350).
See California Department of Public Health's website for certification programs and
testing labs.
https://www.cdph.ca.gov/Programs/CCDPHP/DEODC/EHLB/IAQ/Pages/VOC.aspx
4.504.5
Composite
Wood
Products
Hardwood plywood, particleboard and medium density fiberboard composite wood
products used on the interior or exterior of the building shall meet the requirements
for formaldehyde as specified in ARB's Air Toxics Control Measure for Composite
Wood (17 CCR 93120 et seq.) as shown in Table 4.504.5.
Page 9 of 10
Division 4.5 – Environmental Quality (Interior Moisture Control)
SECTION SHEET REQUIREMENTS
4.505.2
Concrete
Slab
Foundations
Concrete slab foundations required to have a vapor retarder by the California
Building Code, Chapter 19 or concrete slab-on-ground floors required to have a
vapor retarder by the California Residential Code, Chapter 5, shall also comply with
this section.
4.505.2.1 Capillary
Break
A capillary break shall be installed in compliance with at least one of the following:
1. A 4-inch-thick (101.6 mm) base of 1/2 inch (12.7 mm) or larger clean aggregate shall
be provided with a vapor retarder in direct contact with concrete and a concrete mix
design, which will address bleeding, shrinkage and curling, shall be used. For
additional information, see American Concrete Institute, ACI 302.2R-06.
2. Other equivalent methods approved by the enforcing agency.
3. A slab design specified by a licensed design professional.
4.505.3
Moisture
Content of
Building
Materials
Building materials with visible signs of water damage shall not be installed. Wall
and floor framing shall not be enclosed when the framing members exceed 19%
moisture content. Moisture content shall be verified in compliance with the following:
1. Moisture content shall be determined with either a probe-type or contact-type
moisture meter. Equivalent moisture verification methods may be approved by
the enforcing agency and shall satisfy requirements in Section 101.8.
2. Moisture readings shall be taken at a point 2 feet to 4 feet from the grade-
stamped end of each piece to be verified.
3. At least 3 random moisture readings shall be performed on wall and floor
framing with documentation acceptable to the enforcing agency provided at the
time of approval to enclose the wall and floor framing.
Note: Insulation products which are visibly wet or have a high moisture content shall be
replaced or allowed to dry prior to enclosure in wall or floor cavities. Manufacturers’
drying recommendations shall be followed for wet-applied insulation products prior to
enclosure.
4.506.1
Bathroom
Exhaust
Fans
Each bathroom shall be mechanically ventilated and shall comply with the following:
Fans shall be ENERGY STAR compliant and be ducted to terminate outside the
building.
Unless functioning as a component of a whole house ventilation system, fans must
be controlled by a humidity control.
Humidity controls shall be capable of adjustment between a relative humidity range
of ≤ 50 percent to a maximum of 80 percent. A humidity control may utilize manual
or automatic means of adjustment. A humidity control may be a separate
component to the exhaust fan and is not required to be integral (i.e., built-in).
Notes:
- For the purposes of this section, a bathroom is a room which contains a bathtub, shower
or tub/shower combination.
- Lighting integral to bathroom exhaust fans shall comply with the California Energy Code.
Page 10 of 10
Division 4.5 – Environmental Quality (Environmental Comfort)
SECTION SCOPE REQUIREMENTS
4.507.2 HVAC
System Design
Heating and air-conditioning systems shall be sized, designed, and have their
equipment selected using the following methods:
1. The heat loss and heat gain are established according to ANSI/ACCA 2
Manual J—2016 (Residential Load Calculation), ASHRAE handbooks or other
equivalent design software or methods.
2. Duct systems are sized according to ANSI/ACCA 1 Manual D—2016
(Residential Duct Systems), ASHRAE handbooks or other equivalent design
software or methods.
3. Select heating and cooling equipment according to ANSI/ACCA 3 Manual S—
2014 (Residential Equipment Selection) or other equivalent design software or
methods.
Exception: Use of alternate design temperatures necessary to ensure the
systems function are acceptable
END
(REV: 05/10/23:JKF)